Division of Petroleum & Chemical Safety

 

Facility: 2042654 Tank: 2

Click for Facility/Tank Ownership history

Capacity: 50000
Product: Diesel Fuel
Status: Currently in use
Regulated Status Federal
OSFM First Notify Date: 2/11/2008
Current Age: 17
Install Date: 10/10/2007
Last Used Date:
Product Date: 10/29/2007
Petroleum Use: Back-up Generator
CERCLA Substance:
CAS Code:
Removed Date:
Abandoned Material:
Abandoned Date:
Red Tag Issue Date:
Fee Due:
UL Number

Equipment Information

Equipment Type Equipment Install Date Last Passing Test Date Test Expire Date Failed Test Date
Corrosion Prot - Piping Flexible Non-Corrosive 7/2/2007 N/A N/A
Corrosion Prot - Tank Composite Non-Corrosive 7/2/2007 N/A N/A
Leak Detect - Piping Mechanical Other Non-vented check valve N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 8/9/2024 8/9/2025
Leak Detect - Piping Mechanical Pressurized Line Leak Detection Polisher Tank# 2 11/4/2021 8/9/2024 8/9/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus 7/2/2007 8/9/2024 8/9/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 7/2/2007 8/9/2024 8/9/2025
Overfill Prev Device Overfill Alarm Overfill Alarm for Tank# 2 7/2/2007 8/9/2024 8/9/2027
Overfill Prev Device Overfill Drop Tube Valve 12/5/2020 8/9/2024 8/9/2027
Piping Fiberglass Chase N/A N/A
Piping Flexible Double Wall OPW Geoflex 7/2/2007 N/A N/A
Piping Single Wall STP/Tanktop Sump STP Polisher Tank# 2 8/9/2024 8/9/2027
Leak Detect - Piping Sump Sensor 8/9/2024 8/9/2025
Piping Single Wall STP/Tanktop Sump STP#2 Supply Gen. 8/9/2024 8/9/2027
Leak Detect - Piping Sump Sensor 8/9/2024 8/9/2025
Piping Single Wall STP/Tanktop Sump STP#1 Supply Gen. 8/9/2024 8/9/2027
Leak Detect - Piping Sump Sensor 8/9/2024 8/9/2025
Spill Contain Device Single Wall Spill Bucket 12/5/2020 8/9/2024 8/9/2027
Tank Composite Double Wall ACT 100 7/2/2007 N/A N/A

Latest Blended Fuel Compatibility Form

No Compatibility Forms Listed


Additional Tests

Equipment Type Equipment Test Type Test Result Test Date History
Piping Chase Secondary Containment OPW Geoduct non-corrosive flexible secondary piping Precision Test (Piping) Pass 10/15/2020 Show History
Piping Fiberglass Chase Precision Test (Piping) Pass 8/9/2024 Show History
Piping Flexible Double Wall OPW Geoflex Precision Test (Piping) Pass 8/9/2024 Show History