Division of Petroleum & Chemical Safety

 

Facility: 2041253 Tank: 3

Click for Facility/Tank Ownership history

Capacity: 4000
Product: E85
Status: Currently in use
Regulated Status Federal
OSFM First Notify Date: 6/3/2026
Current Age: 23
Install Date: 11/6/2002
Last Used Date:
Product Date:
Petroleum Use: Dispensing
CERCLA Substance:
CAS Code:
Removed Date:
Abandoned Material:
Abandoned Date:
Red Tag Issue Date:
Fee Due: $0.00
UL Number

Equipment Information

Equipment Type Equipment Install Date Last Passing Test Date Test Expire Date Failed Test Date
Corrosion Prot - Piping Flexible Non-Corrosive 4/16/2003 Not applicable Not applicable
Corrosion Prot - Tank Composite Non-Corrosive 4/16/2003 Not applicable Not applicable
Leak Detect - Piping Electronic Pressurized Line Leak Detection 5/27/2026 6/18/2026 6/18/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus 6/18/2026 6/18/2027
Overfill Prev Device Ball Only Removed Ball Float Vent Valve 2/21/2020 Not applicable Not applicable
Overfill Prev Device Overfill Drop Tube Valve 5/27/2026 5/27/2026 5/27/2029
Piping Flexible Double Wall Environ Geo Flex 4/16/2003 Not applicable Not applicable
Piping Single Wall STP/Tanktop Sump 10/9/2019 4/21/2025 4/21/2028
Leak Detect - Piping Sump Sensor with positive shutdown 5/27/2026 6/18/2026 6/18/2027
Spill Contain Device Single Wall Spill Bucket 2/21/2020 4/21/2025 4/21/2028
Tank Composite Double Wall Modern Welding Glasteel II Not applicable Not applicable

Failed test = the latest test has failed.

Not applicable = a test does not apply to this equipment type or configuration.

No passing test found = a passing test is expected but was not found from the source data.


Latest Blended Fuel Compatibility Form

File Name Status Status Date
CompatibilityFormSummary06042026-081820.pdf Approved 6/4/2026

Compatibility Form Attachments

File Name Description
veeder root probes.pdf ATG Probe
Glasteel II BioFuels Compatibility 2018.pdf Composite Double Wall
wayne dispensers all.pdf Dispenser
veeder root plld.pdf Electronic Pressurized Line Leak Detection
Environ+Geo+Flex+Piping.pdf Flexible Double Wall
continental flexsteel hoses.pdf Hose
opw-11bp-series-ethanol-nozzles_2018.pdf Nozzle
FFS-0392 Defender Series OPV Datasheet.pdf Overfill Drop Tube Valve
OPW compatibility.pdf Shear Valve
Opw spill containers.pdf Single Wall Spill Bucket
Environ flexpip4 EPA OUST Letter Piping Suppliers.pdf Single Wall STP/Tanktop Sump
Environ flexpip4 EPA OUST Letter Piping Suppliers.pdf Single Wall UDC Sump
franklin stp.pdf Submersible Turbine Pump
veeder root sensors all.pdf Sump Sensor in Single Wall STP/Tanktop Sump

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date History
Piping Flexible Double Wall Environ Geo Flex Precision Test (Piping) Pass 5/27/2026 Show History