Division of Petroleum & Chemical Safety

 

Facility: 4024426 Tank: 8

Click for Facility/Tank Ownership history

Capacity: 20000
Product: B-99
Status: Currently in use
Regulated Status Federal
OSFM First Notify Date: 9/27/2006
Current Age: 18
Install Date: 6/22/2006
Last Used Date:
Product Date: 6/22/2006
Petroleum Use:
CERCLA Substance:
CAS Code:
Removed Date:
Abandoned Material:
Abandoned Date:
Red Tag Issue Date:
Fee Due: $0.00
UL Number

Equipment Information

Equipment Type Equipment Install Date Last Passing Test Date Test Expire Date Failed Test Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Piping Flexible Non-Corrosive 6/9/2006 N/A N/A
Corrosion Prot - Tank Composite Non-Corrosive 6/9/2006 N/A N/A
Leak Detect - Piping European with No Test Req Suction N/A N/A
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 11/4/2022 9/10/2024 9/10/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 7/19/2024 9/9/2024 9/9/2025
Overfill Prev Device Overfill Drop Tube Valve 11/4/2022 11/11/2023 11/11/2026
Piping Fiberglass Double Wall N/A N/A
Piping Flexible Double Wall OPW Pisces 6/9/2006 N/A N/A
Piping Flex Connector Steel N/A N/A
Piping Single Wall STP/Tanktop Sump 5/7/2022 5/7/2025
Leak Detect - Piping Sump Sensor with positive shutdown 9/9/2024 9/11/2024 9/11/2025
Spill Contain Device Single Wall Spill Bucket 6/9/2006 4/27/2025 4/27/2028
Tank Composite Double Wall 6/9/2006 N/A N/A

Latest Blended Fuel Compatibility Form

File Name Status Status Date
CompatibilityFormSummary12092024-070946.pdf Approved 12/9/2024

Compatibility Form Attachments

File Name Description
VR Mag Plus Probe Biodiesel Compatibility Letter 9-2-22.pdf ATG Probe
VR Mag Plus Probe Biodiesel Compatibility Letter 9-2-22.pdf ATG Probe
Non Descriminating Leak Sensor 794380-321.pdf Bio-heater Tank Top Sump Sensor
Non Descriminating Leak Sensor 794380-321.pdf Bio-heater Tank Top Sump Sensor
highland-tank.pdf Double Walled UST
highland-tank.pdf Double Walled UST
PUMP.pdf European with No Test Req Suction
Dualoy 3000 LCX Data Sheet.pdf Fiberglass Double Wall
Dualoy 3000 LCX Data Sheet.pdf Fiberglass Double Wall
OPW RISER.pdf Flex Connector Steel
opw-fuel-compatibility-matrix-below-ground-products-2018.pdf Flexible Double Wall
opw-fuel-compatibility-matrix-below-ground-products-2018.pdf Flexible Double Wall
INTERSTITIAL SENSOR FIBERGLASS TANK.pdf Non-Discriminating Interstitial Monitoring Sensors
DISPENSER SUMP.pdf Not Installed UDC Sump
opw-71so-t-data-sheet-2018.pdf Overfill Drop Tube Valve
opw-71so-t-data-sheet-2018.pdf Overfill Drop Tube Valve
opw-fuel-compatibility-matrix-below-ground-products-2018.pdf Single Wall Bio-Blender Tank Top Sump
opw-fuel-compatibility-matrix-below-ground-products-2018.pdf Single Wall Bio-Blender Tank Top Sump
opw-fuel-compatibility-matrix-below-ground-products-2018.pdf Single Wall Bio-Blender Tank Top Sump
opw-fuel-compatibility-matrix-below-ground-products-2018.pdf Single Wall Bio-Blender Tank Top Sump
opw-fuel-compatibility-matrix-below-ground-products-2018.pdf Single Wall Bio-heater Tank Top Sump
opw-fuel-compatibility-matrix-below-ground-products-2018.pdf Single Wall Bio-heater Tank Top Sump
opw-fuel-compatibility-matrix-below-ground-products-2018.pdf Single Wall Spill Bucket
opw-fuel-compatibility-matrix-below-ground-products-2018.pdf Single Wall Spill Bucket
OPW SINGLE WALL SUMP.pdf Single Wall Transition Sump
Gorman Rupp Bio Pump.pdf Suction Pump
Gorman Rupp Bio Pump.pdf Suction Pump
SUMP SENSOR POSITIVE SHUT DOWN.pdf Sump Sensor with positive shutdown in Single Wall STP/Tanktop Sump
SUMP SENSOR POSITIVE SHUT DOWN.pdf Sump Sensor with positive shutdown

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date History
Piping Fiberglass Double Wall Precision Test (Piping) Pass 6/24/2020 Show History
Piping Flexible Double Wall OPW Pisces Precision Test (Piping) Pass 1/16/2020 Show History
Tank Composite Double Wall Precision Test (Tank) Pass 1/16/2020 Show History