Division of Petroleum & Chemical Safety

 

Facility: 2046751 Tank: 4

Click for Facility/Tank Ownership history

Capacity: 6000
Product: E85
Status: Currently in use
Regulated Status Federal
OSFM First Notify Date: 6/18/2019
Current Age: 7
Install Date: 2/22/2019
Last Used Date:
Product Date: 2/22/2019
Petroleum Use:
CERCLA Substance:
CAS Code:
Removed Date:
Abandoned Material:
Abandoned Date:
Red Tag Issue Date:
Fee Due: $0.00
UL Number

Equipment Information

Equipment Type Equipment Install Date Last Passing Test Date Test Expire Date Failed Test Date
Corrosion Prot - Piping Cathodic Protection with Dielectric Coating Not applicable Not applicable
Corrosion Prot - Piping Fiberglass Non-Corrosive Not applicable Not applicable
Corrosion Prot - Tank Fiberglass Non-Corrosive Not applicable Not applicable
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 3/27/2026 3/27/2027
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors With Monitor 3/27/2026 3/27/2027
Overfill Prev Device Overfill Drop Tube Valve 2/24/2022 3/17/2025 3/17/2028
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Not applicable Not applicable
Piping Flex Connector Steel Not applicable Not applicable
Piping Single Wall STP/Tanktop Sump 3/17/2025 3/17/2028
Leak Detect - Piping Sump Sensor with positive shutdown 3/27/2026 3/27/2027
Piping Ball Valves Not applicable Not applicable
Piping Extractor Fitting Valves Not applicable Not applicable
Spill Contain Device Double Wall Spill Bucket 3/17/2025 3/17/2028
Tank Fiberglass Double Wall Containment Solutions Not applicable Not applicable

Failed test = the latest test has failed.

Not applicable = a test does not apply to this equipment type or configuration.

No passing test found = a passing test is expected but was not found from the source data.


Latest Blended Fuel Compatibility Form

File Name Status Status Date
CompatibilityFormSummary05172022-155644.pdf Approved 5/17/2022

Compatibility Form Attachments

File Name Description
veeder root probes.pdf ATG Probe
Watts SS Ball Valve ES-S-FBV-1.pdf Ball Valves
gilbarco dispener e85 certification letter.pdf Dispenser
gilbarco dispener e85 certification letter.pdf Dispenser gaskets
Opw spill containers.pdf Double Wall Spill Bucket
EMCO A1100 Overfill Prevention Valve.pdf Emco Wheaton
opw all products.pdf Extractor Fitting Valves
Containment Solutions biofuel-compatibility.pdf Fiberglass Double Wall
ameron fiberglass pipe.pdf Fiberglass Double Wall
opw all products.pdf Flex Connector Steel
red jacket mlld.pdf Mechanical Pressurized Line Leak Detection
veeder root sensors all.pdf Non-Discriminating Interstitial Monitoring Sensors
veeder root sensors all.pdf Non-Discriminating Sump Sensor with positive shutdown in Single Wall STP/Tanktop Sump
franklin stp.pdf Pump gaskets
opw all products.pdf Single Wall Dispenser Sump
opw all products.pdf Single Wall STP/Tanktop Sump
franklin stp.pdf Submersible Pump
SealantReferenceGuide.pdf Thread sealant

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date History
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 4/28/2020 Show History
Tank Fiberglass Double Wall Containment Solutions Precision Test (Tank) Pass 6/17/2019 Show History