Division of Petroleum & Chemical Safety

 

Facility: 6047873 Tank: 7

Click for Facility/Tank Ownership history

Capacity: 12000
Product: B-99
Status: Installed/Not in Use
Regulated Status Federal
OSFM First Notify Date: 4/17/2026
Current Age: 0
Install Date: 5/19/2025
Last Used Date:
Product Date: 4/3/2026
Petroleum Use: Dispensing
CERCLA Substance:
CAS Code:
Removed Date:
Abandoned Material:
Abandoned Date:
Red Tag Issue Date:
Fee Due: $0.00
UL Number E26287672

Equipment Information

Equipment Type Equipment Install Date Last Passing Test Date Test Expire Date Failed Test Date
Leak Detect - Piping Electronic Pressurized Line Leak Detection 4/22/2026 4/22/2026 4/22/2027
Leak Detect - Tank Automatic Tank Gauging Incon TS 550 EVO 4/22/2026 4/22/2026 4/22/2027
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 4/22/2026 4/22/2026 4/22/2027
Overfill Prev Device Overfill Drop Tube Valve 4/6/2026 4/6/2026 4/6/2029
Piping Blending Sump 4/8/2026 7/24/2025 7/24/2028
Leak Detect - Piping Sump Sensor with positive shutdown 4/22/2026 4/22/2026 4/22/2027
Piping Flexible Double Wall Franklin Fueling Systems UPP 4/8/2026 N/A N/A
Piping Flexible Single Wall Piping 4/8/2026 N/A N/A
Piping Single Wall STP/Tanktop Sump 7/24/2025 7/24/2025 7/24/2028
Leak Detect - Piping Sump Sensor with positive shutdown 4/22/2026 4/22/2026 4/22/2027
Spill Contain Device Double Wall Spill Bucket 7/24/2025 7/24/2025 7/24/2028
Tank Fiberglass Double Wall KBK Industries 5/19/2025 N/A N/A

Latest Blended Fuel Compatibility Form

File Name Status Status Date
CompatibilityFormSummary04282025-065922.pdf Approved 4/28/2025

Compatibility Form Attachments

File Name Description
FFS-0434 Digital Inventory & Leak Detection Probes Datasheet.pdf ATG Probe
All Line compatibility email.pdf B99 injection pumps seals
21BVSS - B100 Compatibility.pdf Ball Valves
OPW compatibility matrix.pdf Blending Sump
FFS-0127 Defender Series Spill Containers Datasheet.pdf Double Wall Spill Bucket
FFS-0263 Electronic Line Leak Detection Datasheet.pdf Electronic Pressurized Line Leak Detection
KBK compatibility2.pdf Fiberglass Double Wall
opw-fuel-compatibility-matrix-below-ground-products-2018 (1).pdf Flex Connector Steel
UPP.pdf Flexible Double Wall
UPP.pdf Flexible Single Wall Piping
All Line compatibility email.pdf Injection pump
FFS-0635 Sensors Compatibility Datasheet.pdf Non-Discriminating Interstitial Monitoring Sensors
ISTAPMV4 compatibility.pdf Other Pump
biodiesel compatibility seals.materials chart.pdf Other Riser
NOV Red Thread - Compatible Fuels.pdf Other Riser
FFS-0392 Defender Series OPV Datasheet.pdf Overfill Drop Tube Valve
OPW compatibility matrix.pdf Shear Valve
OPW compatibility matrix.pdf Single Wall STP/Tanktop Sump
FFS-0801 (50Hz) Submersible Turbine Pumps Datasheet.pdf Submersible Turbine Pump
FFS-0635 Sensors Compatibility Datasheet.pdf Sump Sensor with positive shutdown
biofuel-compatibility.pdf Teflon tape

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date History
Piping Blending Sump Precision Test (Piping) Pass 4/8/2026 Show History
Piping Flexible Double Wall Franklin Fueling Systems UPP Precision Test (Piping) Pass 4/8/2026 Show History
Piping Flexible Single Wall Piping Precision Test (Piping) Pass 4/8/2026 Show History
Tank Fiberglass Double Wall KBK Industries Precision Test (Tank) Pass 4/8/2026 Show History