Division of Petroleum & Chemical Safety

 

Facility: 2007971 Tank: 2

Click for Facility/Tank Ownership history

Capacity: 2500
Product: Diesel Fuel
Status: Currently in use
Regulated Status Federal
OSFM First Notify Date: 5/23/2005
Current Age: 19
Install Date: 3/23/2005
Last Used Date:
Product Date: 3/23/2005
Petroleum Use: Back-up Generator
CERCLA Substance:
CAS Code:
Removed Date:
Abandoned Material:
Abandoned Date:
Red Tag Issue Date:
Fee Due: $0.00
UL Number

Equipment Information

Equipment Type Equipment Install Date Last Passing Test Date Test Expire Date Failed Test Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive 5/2/2005 N/A N/A
Leak Detect - Piping American with Annual Prec Line Testing Suction 1/25/2024 1/25/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 5/2/2005 1/25/2024 1/25/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 5/2/2005 1/25/2024 1/25/2025
Overfill Prev Device Overfill Alarm 5/2/2005 1/30/2023 1/30/2026
Overfill Prev Device Overfill Drop Tube Valve 6/8/2023 6/8/2023 6/8/2026
Piping Fiberglass Chase N/A N/A
Piping Steel Single Wall Piping N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated N/A N/A
Spill Contain Device Double Wall Spill Bucket 6/8/2023 6/8/2023 6/8/2026
Tank Fiberglass Double Wall Containment Solutions 5/2/2005 N/A N/A

Latest Blended Fuel Compatibility Form

No Compatibility Forms Listed


Additional Tests

Equipment Type Equipment Test Type Test Result Test Date History
Piping Fiberglass Chase Precision Test Pass 1/25/2024 Show History
Piping Fiberglass Secondary Containment Steel primary Precision Test Pass 1/19/2021 Show History
Piping Steel Single Wall Piping Precision Test Pass 1/25/2024 Show History