Division of Petroleum & Chemical Safety

 

Facility: 2033566 Tank: 1

Click for Facility/Tank Ownership history

Capacity: 20000
Product: Diesel Fuel
Status: Currently in use
Regulated Status Federal
OSFM First Notify Date: 10/21/1988
Current Age: 36
Install Date: 6/15/1988
Last Used Date:
Product Date: 6/15/1988
Petroleum Use: Back-up Generator
CERCLA Substance:
CAS Code:
Removed Date:
Abandoned Material:
Abandoned Date:
Red Tag Issue Date:
Fee Due: $0.00
UL Number

Equipment Information

Equipment Type Equipment Install Date Last Passing Test Date Test Expire Date Failed Test Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 2/21/2025 2/21/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 with CSLD 2/24/2022 2/21/2025 2/21/2026
Leak Detect - Tank Hydrostatic Reservoir Interstitial Monitoring Sensors 4/8/2022 2/21/2025 2/21/2026
Overfill Prev Device Overfill Drop Tube Valve 2/21/2022 2/21/2025 2/21/2028
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Double Wall STP/Tanktop Sump 1/11/2022 4/5/2024 4/5/2027
Leak Detect - Piping Sump Sensor 1/11/2022 2/21/2025 2/21/2026
Piping Double Wall Transition Sump West 4/5/2024 4/5/2027
Leak Detect - Piping Sump Sensor 2/21/2025 2/21/2026
Piping Double Wall Transition Sump East 4/5/2024 4/5/2027
Leak Detect - Piping Sump Sensor 2/21/2025 2/21/2026
Piping Double Wall Transition Sump Center 4/5/2024 4/5/2027
Leak Detect - Piping Sump Sensor 2/21/2025 2/21/2026
Spill Contain Device Single Wall Spill Bucket 9/14/2021 4/5/2024 4/5/2027
Tank Fiberglass Double Wall Owens Corning Brine Filled N/A N/A

Latest Blended Fuel Compatibility Form

No Compatibility Forms Listed


Additional Tests

Equipment Type Equipment Test Type Test Result Test Date History
Leak Detect - Piping American with Annual Prec Line Testing Suction Functional Pass 4/1/2020 Show History
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 2/21/2025 Show History
Piping Fiberglass Secondary Containment Steel primary Precision Test (Piping) Pass 4/1/2020 Show History