Division of Petroleum & Chemical Safety

 

Facility: 6011123 Tank: 3

Click for Facility/Tank Ownership history

Capacity: 12000
Product: Gasoline - Regular
Status: Currently in use
Regulated Status Federal
OSFM First Notify Date: 3/25/1988
Current Age: 37
Install Date: 3/1/1988
Last Used Date:
Product Date: 3/25/1988
Petroleum Use:
CERCLA Substance:
CAS Code:
Removed Date:
Abandoned Material:
Abandoned Date:
Red Tag Issue Date:
Fee Due: $0.00
UL Number

Equipment Information

Equipment Type Equipment Install Date Last Passing Test Date Test Expire Date Failed Test Date
Corrosion Prot - Piping Isolation Boots Flex Connector N/A N/A
Corrosion Prot - Piping Sacrificial Anode Flex Connector STP 4/26/2021 5/3/2024 5/3/2027
Corrosion Prot - Piping Fiberglass Non-Corrosive 10/16/2003 N/A N/A
Corrosion Prot - Tank Sacrificial Anode Cathodic Protection 5/3/2024 5/3/2027
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 5/7/2025 5/7/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus with CSLD 5/7/2025 5/7/2026
Overfill Prev Device Overfill Drop Tube Valve 7/5/2019 6/6/2022 6/6/2025
Piping Flex Connector Steel N/A N/A
Piping Fiberglass Single Wall Piping Ameron 10/16/2003 N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Single Wall Spill Bucket 5/7/2025 5/7/2028
Tank STIP3 Single Wall N/A N/A
Vent, Riser, Fill Piping Steel risers N/A N/A

Latest Blended Fuel Compatibility Form

No Compatibility Forms Listed


Additional Tests

Equipment Type Equipment Test Type Test Result Test Date History
Piping Fiberglass Single Wall Piping Ameron Precision Test (Piping) Pass 5/7/2025 Show History
Leak Detect - Tank SIR and Prec Tightness Testing USTman Industries Precision Test (Tank) Pass 9/23/2013 Show History