Division of Petroleum & Chemical Safety

 

Facility: 2045701 Tank: 2

Click for Facility/Tank Ownership history

Capacity: 40000
Product: Diesel Fuel
Status: Currently in use
Regulated Status Federal
OSFM First Notify Date: 6/23/2015
Current Age: 9
Install Date: 10/23/2014
Last Used Date:
Product Date: 11/6/2015
Petroleum Use: Back-up Generator
CERCLA Substance:
CAS Code:
Removed Date:
Abandoned Material:
Abandoned Date:
Red Tag Issue Date:
Fee Due:
UL Number

Equipment Information

Equipment Type Equipment Install Date Last Passing Test Date Test Expire Date Failed Test Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Composite Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Other Non-vented check valve South N/A N/A
Leak Detect - Piping Mechanical Other Non-vented check valve North N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 9/25/2024 9/25/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus 9/25/2024 9/25/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 9/25/2024 9/25/2025
Manway At Grade Accessible Manway Accessible at Grade N/A N/A
Overfill Prev Device Overfill Alarm Tanks 1 and 2 9/26/2024 9/26/2027
Overfill Prev Device Overfill Drop Tube Valve 9/26/2024 9/26/2027
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump Tank Top Sump North 9/26/2024 9/26/2027
Leak Detect - Piping Sump Sensor for emergency backup generator only 12/12/2024 12/12/2024 12/12/2025
Piping Single Wall STP/Tanktop Sump Tank Top Sump South Center 9/26/2024 9/26/2027
Leak Detect - Piping Sump Sensor 9/25/2024 9/25/2025
Piping Single Wall STP/Tanktop Sump Tank Top Sump South Polisher with Mechanical LD. 9/26/2024 9/26/2027
Leak Detect - Piping Sump Sensor 9/25/2024 9/25/2025
Piping Single Wall Transition Sump Transition Sump North Polisher 9/26/2024 9/26/2027
Leak Detect - Piping Sump Sensor 9/25/2024 9/25/2025
Piping Single Wall Transition Sump Transition Sump North Center T2 9/26/2024 9/26/2027
Leak Detect - Piping Sump Sensor 9/28/2023 9/25/2024 9/25/2025
Spill Contain Device Single Wall Spill Bucket 9/26/2024 9/26/2027
Tank Composite Double Wall ACT 100 N/A N/A

Latest Blended Fuel Compatibility Form

No Compatibility Forms Listed


Additional Tests

Equipment Type Equipment Test Type Test Result Test Date History
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 9/25/2024 Show History