Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 7047550
Status: Active
Facility Name: QT #7190
Address: 4501 Veterans Memorial Drive Mount Vernon, IL 62864
County: Jefferson
Property Parcel: 1002200010
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y003419
Green Tag Issue Date: 10/5/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: QuikTrip Corporation
Owner Address: 4705 South 129th East Ave. Tulsa, OK 74134
Owner Status: Current Owner
Purchase Date:
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 4/11/2026

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 10/5/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0034559 QuikTrip Corporation, Current Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020251621 (Pending)    Issue Date: 6/27/2025    Expiration Date: 8/26/2025    View NOV Form

Tanks Violations
Facility A/B operator retraining required as a result of issuance of the Notice of Violation
Facility Annual Emergency Stop Inspection not completed or inspection report not available. - Report is not completed, Facility has 7 E-Stops only 6 tested.
1, 2, 4, 5, 6, 7, 8 Line interstitial sensors have been raised and rendered inoperational. - Dispenser #17 raised sensor
6 Line leak detection equipment in alarm or failed test, must repair or replace. - L33 T6 DSL-Auto STP sump removed from programming.
2, 3, 4 Miscellaneous - 174.370 General Requirement to Maintain All Equipment
6 Miscellaneous - Spill prevention equipment device requires repair
Facility Missing copies of 30 day Walkthrough Inspection Report. - 2 years of records required.
Facility Missing copies of Annual Walkthrough Inspection Report.
1, 2, 3, 4, 5, 6, 7, 8 Monthly line interstitial sensor records not available. - Records must be available for the previous 2 years.
1, 2, 3, 4, 5, 6, 7, 8 Piping interstitial must be open in all sumps - Dispensers 2-18
6 Precision line test required. - Line leaking at T6 STP sump, repair leak, remove product and test the line.
1, 2, 3, 4, 5, 6, 7, 8 Required monthly tank interstitial sensor records not available. - Records must be available for the previous 2 years.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 20000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 9/25/2023 Abandoned Material:
Current Age: 1 Abandoned Date:
Install Date: 5/25/2023 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 9/8/2023

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 8/25/2024 8/25/2025
Leak Detect - Piping Electronic Pressurized Line Leak Detection 8/25/2024 8/25/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 8/25/2024 8/25/2025
Leak Detect - Tank Hydrostatic Reservoir Interstitial Monitoring Sensors 8/25/2024 8/25/2025
Overfill Prev Device Overfill Drop Tube Valve 6/13/2023 6/13/2026
Piping Flexible Double Wall Franklin Fueling Systems UPP N/A N/A
Piping Single Wall STP/Tanktop Sump 7/5/2023 7/5/2026
Leak Detect - Piping Sump Sensor with positive shutdown 8/25/2024 8/25/2025
Piping Single Wall Transition Sump 7/5/2023 7/5/2026
Leak Detect - Piping Sump Sensor with positive shutdown 8/25/2024 8/25/2025
Spill Contain Device Double Wall Spill Bucket 7/5/2023 7/5/2026
Tank Fiberglass Brine Filled Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Franklin Fueling Systems UPP Precision Test (Piping) Pass 10/4/2023
Tank Fiberglass Brine Filled Double Wall XERXES Precision Test (Tank) Pass 10/4/2023



Tank Number 2

Capacity: 20000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 9/25/2023 Abandoned Material:
Current Age: 1 Abandoned Date:
Install Date: 5/25/2023 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 9/8/2023

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Other Non-vented check valve N/A N/A
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 8/25/2024 8/25/2025
Leak Detect - Tank Hydrostatic Reservoir Interstitial Monitoring Sensors 8/25/2024 8/25/2025
Overfill Prev Device Overfill Drop Tube Valve 6/13/2023 6/13/2026
Piping Flexible Double Wall Franklin Fueling Systems UPP N/A N/A
Piping Single Wall STP/Tanktop Sump 7/5/2023 7/5/2026
Leak Detect - Piping Sump Sensor with positive shutdown 8/25/2024 8/25/2025
Piping Single Wall Transition Sump 7/5/2023 7/5/2026
Leak Detect - Piping Sump Sensor with positive shutdown 8/25/2024 8/25/2025
Spill Contain Device Double Wall Spill Bucket 7/5/2023 7/5/2026
Tank Fiberglass Brine Filled Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Franklin Fueling Systems UPP Precision Test (Piping) Pass 10/4/2023
Tank Fiberglass Brine Filled Double Wall XERXES Precision Test (Tank) Pass 10/4/2023



Tank Number 3

Capacity: 20000 Petroleum Use:
Product: Gasoline - Non Ethanol CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 9/25/2023 Abandoned Material:
Current Age: 1 Abandoned Date:
Install Date: 5/25/2023 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 9/8/2023

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 8/25/2024 8/25/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 8/25/2024 8/25/2025
Leak Detect - Tank Hydrostatic Reservoir Interstitial Monitoring Sensors 8/25/2024 8/25/2025
Overfill Prev Device Overfill Drop Tube Valve 6/13/2023 6/13/2026
Piping Flexible Double Wall Franklin Fueling Systems UPP N/A N/A
Piping Single Wall STP/Tanktop Sump 7/5/2023 7/5/2026
Leak Detect - Piping Sump Sensor with positive shutdown 8/25/2024 8/25/2025
Piping Single Wall Transition Sump 7/5/2023 7/5/2026
Leak Detect - Piping Sump Sensor with positive shutdown 8/25/2024 8/25/2025
Spill Contain Device Double Wall Spill Bucket 7/5/2023 7/5/2026
Tank Fiberglass Brine Filled Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Franklin Fueling Systems UPP Precision Test (Piping) Pass 10/4/2023
Tank Fiberglass Brine Filled Double Wall XERXES Precision Test (Tank) Pass 10/4/2023



Tank Number 4

Capacity: 20000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 9/25/2023 Abandoned Material:
Current Age: 1 Abandoned Date:
Install Date: 5/25/2023 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 9/8/2023

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 8/25/2024 8/25/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 8/25/2024 8/25/2025
Leak Detect - Tank Hydrostatic Reservoir Interstitial Monitoring Sensors 8/25/2024 8/25/2025
Overfill Prev Device Overfill Drop Tube Valve 6/13/2023 6/13/2026
Piping Flexible Double Wall Franklin Fueling Systems UPP N/A N/A
Piping Single Wall STP/Tanktop Sump 7/5/2023 7/5/2026
Leak Detect - Piping Sump Sensor with positive shutdown 8/25/2024 8/25/2025
Piping Single Wall Transition Sump 7/5/2023 7/5/2026
Leak Detect - Piping Sump Sensor with positive shutdown 8/25/2024 8/25/2025
Spill Contain Device Double Wall Spill Bucket 7/5/2023 7/5/2026
Tank Fiberglass Brine Filled Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Franklin Fueling Systems UPP Precision Test (Piping) Pass 10/4/2023
Tank Fiberglass Brine Filled Double Wall XERXES Precision Test (Tank) Pass 10/4/2023



Tank Number 5

Capacity: 18000 Petroleum Use: None
Product: B-99 CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 9/25/2023 Abandoned Material:
Current Age: 1 Abandoned Date:
Install Date: 5/18/2023 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 9/8/2023

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 8/25/2024 8/25/2025
Leak Detect - Piping Electronic Pressurized Line Leak Detection 8/25/2024 8/25/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 8/25/2024 8/25/2025
Leak Detect - Tank Hydrostatic Reservoir Interstitial Monitoring Sensors 8/25/2024 8/25/2025
Overfill Prev Device Overfill Drop Tube Valve 6/13/2023 6/13/2026
Piping Flexible Double Wall Franklin Fueling Systems UPP N/A N/A
Piping Single Wall STP/Tanktop Sump 7/25/2023 7/25/2026
Leak Detect - Piping Sump Sensor with positive shutdown 8/25/2024 8/25/2025
Piping Single Wall Transition Sump 7/25/2023 7/25/2026
Leak Detect - Piping Sump Sensor with positive shutdown 8/25/2024 8/25/2025
Spill Contain Device Double Wall Spill Bucket 7/25/2023 7/25/2026
Tank Fiberglass Brine Filled Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Franklin Fueling Systems UPP Precision Test (Piping) Pass 10/4/2023
Tank Fiberglass Brine Filled Double Wall XERXES Precision Test (Tank) Pass 10/4/2023



Tank Number 6

Capacity: 30000 Petroleum Use: None
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 9/25/2023 Abandoned Material:
Current Age: 1 Abandoned Date:
Install Date: 5/18/2023 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 9/8/2023

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 8/25/2024 8/25/2025
Leak Detect - Piping Electronic Pressurized Line Leak Detection 8/25/2024 8/25/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 8/25/2024 8/25/2025
Leak Detect - Tank Hydrostatic Reservoir Interstitial Monitoring Sensors 8/25/2024 8/25/2025
Overfill Prev Device Overfill Drop Tube Valve 6/13/2023 6/13/2026
Piping Flexible Double Wall Franklin Fueling Systems UPP N/A N/A
Piping Single Wall STP/Tanktop Sump 7/25/2023 7/25/2026
Leak Detect - Piping Sump Sensor with positive shutdown 8/25/2024 8/25/2025
Piping Single Wall Transition Sump 7/25/2023 7/25/2026
Leak Detect - Piping Sump Sensor with positive shutdown 8/25/2024 8/25/2025
Spill Contain Device Double Wall Spill Bucket 7/25/2023 7/25/2026
Tank Fiberglass Brine Filled Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Franklin Fueling Systems UPP Precision Test (Piping) Pass 10/4/2023
Tank Fiberglass Brine Filled Double Wall XERXES Precision Test (Tank) Pass 10/4/2023



Tank Number 7

Capacity: 30000 Petroleum Use: None
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 9/25/2023 Abandoned Material:
Current Age: 1 Abandoned Date:
Install Date: 5/18/2023 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 9/8/2023

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Other Non-vented check valve N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 8/25/2024 8/25/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 8/25/2024 8/25/2025
Leak Detect - Tank Hydrostatic Reservoir Interstitial Monitoring Sensors 8/25/2024 8/25/2025
Overfill Prev Device Overfill Drop Tube Valve 6/13/2023 6/13/2026
Piping Flexible Double Wall Franklin Fueling Systems UPP N/A N/A
Piping Single Wall STP/Tanktop Sump 7/25/2023 7/25/2026
Leak Detect - Piping Sump Sensor with positive shutdown 8/25/2024 8/25/2025
Piping Single Wall Transition Sump 7/25/2023 7/25/2026
Leak Detect - Piping Sump Sensor with positive shutdown 8/25/2024 8/25/2025
Spill Contain Device Double Wall Spill Bucket 7/25/2023 7/25/2026
Tank Fiberglass Brine Filled Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Franklin Fueling Systems UPP Precision Test (Piping) Pass 10/4/2023
Tank Fiberglass Brine Filled Double Wall XERXES Precision Test (Tank) Pass 10/4/2023



Tank Number 8

Capacity: 30000 Petroleum Use: None
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 9/25/2023 Abandoned Material:
Current Age: 1 Abandoned Date:
Install Date: 5/18/2023 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 9/8/2023

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Other Non-vented check valve N/A N/A
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 8/25/2024 8/25/2025
Leak Detect - Tank Hydrostatic Reservoir Interstitial Monitoring Sensors 8/25/2024 8/25/2025
Overfill Prev Device Overfill Drop Tube Valve 6/13/2023 6/13/2026
Piping Flexible Double Wall Franklin Fueling Systems UPP N/A N/A
Piping Single Wall STP/Tanktop Sump 7/25/2023 7/25/2026
Leak Detect - Piping Sump Sensor with positive shutdown 8/25/2024 8/25/2025
Piping Single Wall Transition Sump 7/25/2023 7/25/2026
Leak Detect - Piping Sump Sensor with positive shutdown 8/25/2024 8/25/2025
Spill Contain Device Double Wall Spill Bucket 7/25/2023 7/25/2026
Tank Fiberglass Brine Filled Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Franklin Fueling Systems UPP Precision Test (Piping) Pass 10/4/2023
Tank Fiberglass Brine Filled Double Wall XERXES Precision Test (Tank) Pass 10/4/2023

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 7/25/2023 7/25/2026
Leak Detect - Piping Sump Sensor with positive shutdown 8/25/2024 8/25/2025



Name\ID 1/2 Diesel

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 7/25/2023 7/25/2026
Leak Detect - Piping Sump Sensor with positive shutdown 8/25/2024 8/25/2025



Name\ID 11/12

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 7/25/2023 7/25/2026
Leak Detect - Piping Sump Sensor with positive shutdown 8/25/2024 8/25/2025



Name\ID 13/14

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 7/25/2023 7/25/2026
Leak Detect - Piping Sump Sensor with positive shutdown 8/25/2024 8/25/2025



Name\ID 15/16

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 7/25/2023 7/25/2026
Leak Detect - Piping Sump Sensor with positive shutdown 8/25/2024 8/25/2025



Name\ID 17/18

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 7/25/2023 7/25/2026
Leak Detect - Piping Sump Sensor with positive shutdown 8/25/2024 8/25/2025



Name\ID 19/20

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 7/25/2023 7/25/2026
Leak Detect - Piping Sump Sensor with positive shutdown 8/25/2024 8/25/2025



Name\ID 2/3 Diesel

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 7/25/2023 7/25/2026
Leak Detect - Piping Sump Sensor with positive shutdown 8/25/2024 8/25/2025



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 7/25/2023 7/25/2026
Leak Detect - Piping Sump Sensor with positive shutdown 8/25/2024 8/25/2025



Name\ID 3/4 Diesel

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 7/25/2023 7/25/2026
Leak Detect - Piping Sump Sensor with positive shutdown 8/25/2024 8/25/2025



Name\ID 4/5 Diesel

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 7/25/2023 7/25/2026
Leak Detect - Piping Sump Sensor with positive shutdown 8/25/2024 8/25/2025



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 7/25/2023 7/25/2026
Leak Detect - Piping Sump Sensor with positive shutdown 8/25/2024 8/25/2025



Name\ID 5/6 Diesel

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 7/25/2023 7/25/2026
Leak Detect - Piping Sump Sensor with positive shutdown 8/25/2024 8/25/2025



Name\ID 6/7 Diesel

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 7/25/2023 7/25/2026
Leak Detect - Piping Sump Sensor with positive shutdown 8/25/2024 8/25/2025



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 7/25/2023 7/25/2026
Leak Detect - Piping Sump Sensor with positive shutdown 8/25/2024 8/25/2025



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 7/25/2023 7/25/2026
Leak Detect - Piping Sump Sensor with positive shutdown 8/25/2024 8/25/2025

MFD Motorfuel Dispensing Forms

Facility Number Name City Received Date Letter
7047550 QT #7190 Mount Vernon 09/21/2023 Letter Form