Notice of Violations (Current)
NOV Number:
E0020262125
(Pending)
Issue Date:
8/21/2026
Expiration Date:
10/20/2026
View NOV Form
| Tanks |
Violations |
| 1, 2 |
Annual electronic line leak detector test not completed. |
| Facility |
Annual Emergency Stop Inspection not completed or inspection report not available. |
| 1, 2 |
Annual leak detection certification not completed (Required annually). |
| 1, 2 |
Line interstitial sensor functional test not accomplished (Required annually). |
| Facility |
Missing copies of Annual Walkthrough Inspection Report. |
| 1, 2 |
Piping interstitial must be open in all sumps - Dispenser 3/4 only. |
| 1, 2 |
Shear valve inspection report not completed (Required during Annual Walkthrough Inspection). |
| 2 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. - Diesel spill bucket is full of liquid. |
| 1, 2 |
Tank interstitial sensor functional test not accomplished (Required annually). |
IEMA Numbers Associated with the Facility
No IEMA Numbers Found
LUST
Fund Eligibility and Deductibility Determinations
No Applications Found
Tank Number 1
| Capacity: |
12000 |
|
Petroleum Use: |
|
| Product: |
Gasoline - Regular |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
12/6/2019 |
|
Abandoned Material: |
|
| Current Age: |
6 |
|
Abandoned Date: |
|
| Install Date: |
12/5/2019 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
|
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Flexible Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Composite Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Electronic Pressurized Line Leak Detection |
7/25/2025 |
7/25/2026 |
|
Leak Detect - Tank
|
Non-Discriminating Interstitial Monitoring Sensors With Monitor |
7/25/2025 |
7/25/2026 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
7/25/2025 |
7/25/2028 |
|
Piping
|
Flexible Double Wall OmegaFlex DoubleTrac |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
7/25/2025 |
7/25/2028 |
Leak Detect - Piping
|
Sump Sensor with positive shutdown |
7/25/2025 |
7/25/2028 |
|
Spill Contain Device
|
Double Wall Spill Bucket |
7/25/2025 |
7/25/2028 |
|
Tank
|
Composite Double Wall Modern Welding Glasteel II |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Flexible Double Wall OmegaFlex DoubleTrac
|
Precision Test (Piping)
|
Pass
|
9/4/2024
|
|
Tank
|
Composite Double Wall Modern Welding Glasteel II
|
Precision Test (Tank)
|
Pass
|
9/4/2024
|
Tank Number 2
| Capacity: |
8000 |
|
Petroleum Use: |
None |
| Product: |
Diesel Fuel |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
12/6/2019 |
|
Abandoned Material: |
|
| Current Age: |
6 |
|
Abandoned Date: |
|
| Install Date: |
12/5/2019 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
|
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Flexible Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Composite Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Electronic Pressurized Line Leak Detection |
7/25/2025 |
7/25/2026 |
|
Leak Detect - Tank
|
Non-Discriminating Interstitial Monitoring Sensors With Monitor |
7/25/2025 |
7/25/2026 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
7/25/2025 |
7/25/2028 |
|
Piping
|
Flexible Double Wall OmegaFlex DoubleTrac |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
7/25/2025 |
7/25/2028 |
Leak Detect - Piping
|
Sump Sensor with positive shutdown |
7/25/2025 |
7/25/2028 |
|
Spill Contain Device
|
Double Wall Spill Bucket |
7/25/2025 |
7/25/2028 |
|
Tank
|
Composite Double Wall Modern Welding Glasteel II |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Flexible Double Wall OmegaFlex DoubleTrac
|
Precision Test (Piping)
|
Pass
|
9/4/2024
|
|
Tank
|
Composite Double Wall Modern Welding Glasteel II
|
Precision Test (Tank)
|
Pass
|
9/4/2024
|
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
Dispenser Information
Name\ID 1/2
| Status: |
Active |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Single Wall UDC Sump |
7/25/2025
|
7/25/2028
|
Leak Detect - Piping
|
Sump Sensor with positive shutdown |
7/25/2025
|
7/25/2026
|
Name\ID 3/4
| Status: |
Active |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Single Wall UDC Sump |
7/25/2025
|
7/25/2028
|
Leak Detect - Piping
|
Sump Sensor with positive shutdown |
7/25/2025
|
7/25/2026
|
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
MFD
Motorfuel Dispensing Forms
| Facility Number |
Name |
City |
Received Date |
Letter |
|
7046960
|
Big Daddy Liquor, Inc.
|
Pittsburg
|
01/30/2020
|
Letter
Form
|
|
7046960
|
Big Daddy Liquor, Inc.
|
Pittsburg
|
10/31/2019
|
Letter
Form
|