Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 7045943
Status: Active
Facility Name: Hucks
Address: 1107 Oak Street Carmi, IL 62821
County: White
Property Parcel:
Facility Type: Unattended Self-Service Station
Owner Type: Private
Green Tag Decal: Y003445
Green Tag Issue Date: 2/14/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: Martin & Bayley, Inc.
Owner Address: P.O. Box 385 Carmi, IL 62821
Owner Status: Current Owner
Purchase Date:
Type of Financial Responsibility: Self-Insurance
Financial Responsibility Reporting Due Date: 12/25/2025

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Unattended Self Service 2/14/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0009763 Martin & Bayley, Inc. Current Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020252322 (Pending)    Issue Date: 9/4/2025    Expiration Date: 11/3/2025    View NOV Form

Tanks Violations
Facility Emergency contact information for A/B & C Operators not posted at unmanned facility
2 Line interstitial sensors have been raised and rendered inoperational. - Dispenser #2 sump sensor raised out of liquid.
2 Miscellaneous - Piping leak detection equipment upgraded without approved OSFM permit.
1, 2 Piping interstitial must be open in all sumps
Facility Submit Notification Form for Facility Information Change - Address of facility needs to be changed to the street address. The Notification Form is available at https://webapps.sfm.illinois.gov/USTPortal/NotificationForm

NOV Number: E0020252323 (Pending)    Issue Date: 9/4/2025    Expiration Date: 11/3/2025    View NOV Form

Tanks Violations
Facility Code complying instruction/warning signs are not properly mounted at each dispenser island - Minimum Signage. Signs shall be posted in all-weather materials by each actuator (or at the dispenser if the actuator is an integral part of the dispenser) and the lettering shall be not less than ? inch high. The top of the signs shall be mounted no higher than 10 feet above grade, or at a height approved by OSFM, and shall include the following wording, at a minimum: 1) "No smoking"; 2) "Turn off engine"; 3) "Containers for gasoline must be red"; 4) "Containers for kerosene must be blue"; 5) "It is dangerous and unlawful to fill unapproved containers with gasoline, diesel or kerosene"; 6) "In case of fire or spill use EMERGENCY STOP located at…" (owner must insert the locations of the emergency stops); 7) "EMERGENCY STOP activation transmits a fire alarm to the fire department".
Facility Miscellaneous - A sign shall be placed at each emergency stop stating that activation of the emergency stop "transmits a fire alarm to the fire department"
Facility Miscellaneous - Annual Fire Detection Test has not been performed and/or records of testing are not available.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 10000 Gasoline - Regular Currently in use Federal $0.00
2 10000 Diesel Fuel Currently in use Federal $0.00
3 6000 Diesel Exhaust Fluid (Non-Regulated) Unknown Non-Regulated

Dispenser Information

Name\ID Status
1 Active
2 Active
2S/3 Active
3S Active
4 Active

MFD Motorfuel Dispensing Forms

No Forms Found