| 3, 4, 5 |
Dispensers - hoses cracked, split or worn and require replacement - Dispenser 2,5,6 Reg. Whip Hose, Dispenser 4 Diesel Swivel needs replaced, 17M,17S,19M,21M,21S Hoses need to be replaced. |
| 1, 2, 3, 4, 5 |
Drop tube valve or overfill alarm failed inspection. Repair or replace equipment. - Failed testing 4/24/2025 |
| 4 |
Install or replace lockable fill pipe caps. - Tank #4 Fill cap is loose. |
| 4, 5 |
Line leak detection equipment in alarm or failed test, must repair or replace. - Tank #4 Leak detector north/ south, Tank #5 Leak detector north/ south. |
| 1, 2, 3, 4, 5 |
Piping interstitial must be open in all sumps - All Sumps STP's/UDC's. Gas Dispenser are all opened. |