Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 7045592
Status: Active
Facility Name: Casey's #3391
Address: 2314 W. Main street Marion, IL 62959
County: Williamson
Property Parcel: 06-14-450-035
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Z001097
Green Tag Issue Date: 11/1/2024
Green Tag Expire Date: 12/31/2026
MFD Type: Self Service

Owner Details

Owner Name: Casey's Retail Company
Owner Address: 3305 SE Delaware Ave. P.O. Box 3004 Ankeny, IA 50021
Owner Status: Current Owner
Purchase Date:
Type of Financial Responsibility: Self-Insurance
Financial Responsibility Reporting Due Date: 1/29/2027

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0002560 Casey's Retail Company Current Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violations (Current)

NOV Number: E0020261385 (Pending)    Issue Date: 5/27/2026    Expiration Date: 7/26/2026    View NOV Form

Tanks Violations
1 Submit Notification Form for Product Change - Regular unleaded is now E-15
1 The Blended Fuel Compatibility Form for products greater than E10 and B20 has not been submitted as required.
3 The following dispenser hoses or emergency breakaway devices are actively leaking and require immediate repair (bagged at inspection) - Diesel hose connections leaking.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 20000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 10/1/2014 Abandoned Material:
Current Age: 12 Abandoned Date:
Install Date: 6/12/2014 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment Information

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive Not applicable Not applicable
Corrosion Prot - Tank Fiberglass Non-Corrosive Not applicable Not applicable
Leak Detect - Piping Electronic Pressurized Line Leak Detection 12/3/2025 12/3/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 12/3/2025 12/3/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 12/3/2025 12/3/2026
Overfill Prev Device Overfill Drop Tube Valve 4/18/2024 4/18/2027
Piping Flexible Double Wall A.P.T. Poly Tech P175SC Not applicable Not applicable
Piping STP/Tanktop Sump containment FRP 1/22/2024 1/22/2027
Leak Detect - Piping Sump Sensor with positive shutdown 1/22/2024 1/22/2027
Piping Single Wall STP/Tanktop Sump 1/22/2024 1/22/2027
Leak Detect - Piping Sump Sensor with positive shutdown 1/22/2024 1/22/2027
Spill Contain Device Double Wall Spill Bucket 3/15/2024 3/15/2027
Tank Fiberglass Double Wall Containment Solutions Not applicable Not applicable

Additional Tests

No Tests Listed




Tank Number 2

Capacity: 12000 Petroleum Use:
Product: B-11 CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 10/1/2014 Abandoned Material:
Current Age: 12 Abandoned Date:
Install Date: 6/12/2014 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment Information

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive Not applicable Not applicable
Corrosion Prot - Tank Fiberglass Non-Corrosive Not applicable Not applicable
Leak Detect - Piping Electronic Pressurized Line Leak Detection 12/3/2025 12/3/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 12/3/2025 12/3/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 12/3/2025 12/3/2026
Overfill Prev Device Overfill Drop Tube Valve 1/22/2024 1/22/2027
Piping Flexible Double Wall A.P.T. Poly Tech P175SC Not applicable Not applicable
Piping STP/Tanktop Sump containment FRP 1/22/2024 1/22/2027
Leak Detect - Piping Sump Sensor with positive shutdown 1/22/2024 1/22/2027
Spill Contain Device Double Wall Spill Bucket 1/22/2024 1/22/2027
Tank Fiberglass Double Wall Containment Solutions Not applicable Not applicable

Additional Tests

No Tests Listed




Tank Number 3

Capacity: 8000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 10/1/2014 Abandoned Material:
Current Age: 12 Abandoned Date:
Install Date: 6/12/2014 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment Information

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive Not applicable Not applicable
Corrosion Prot - Tank Fiberglass Non-Corrosive Not applicable Not applicable
Leak Detect - Piping Electronic Pressurized Line Leak Detection 12/3/2025 12/3/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 12/3/2025 12/3/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 12/3/2025 12/3/2026
Overfill Prev Device Overfill Drop Tube Valve 11/1/2024 11/1/2027
Piping Flexible Double Wall A.P.T. Poly Tech P175SC Not applicable Not applicable
Piping STP/Tanktop Sump containment FRP 1/22/2024 1/22/2027
Leak Detect - Piping Sump Sensor with positive shutdown 1/22/2024 1/22/2027
Spill Contain Device Double Wall Spill Bucket 11/1/2024 11/1/2027
Tank Fiberglass Double Wall Containment Solutions Not applicable Not applicable

Additional Tests

No Tests Listed


Failed test = the latest test has failed.

Not applicable = a test does not apply to this equipment type or configuration.

No passing test found = a passing test is expected but was not found from the source data.


Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 1/22/2024 1/22/2027
Leak Detect - Piping Sump Sensor with positive shutdown 12/3/2025 12/3/2026



Name\ID 11/12

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 1/22/2024 1/22/2027
Leak Detect - Piping Sump Sensor with positive shutdown 12/3/2025 12/3/2026



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 1/22/2024 1/22/2027
Leak Detect - Piping Sump Sensor with positive shutdown 12/3/2025 12/3/2026



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 1/22/2024 1/22/2027
Leak Detect - Piping Sump Sensor with positive shutdown 12/3/2025 12/3/2026



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 1/22/2024 1/22/2027
Leak Detect - Piping Sump Sensor with positive shutdown 12/3/2025 12/3/2026



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 1/22/2024 1/22/2027
Leak Detect - Piping Sump Sensor with positive shutdown 12/3/2025 12/3/2026

Failed test = the latest test has failed.

Not applicable = a test does not apply to this equipment type or configuration.

No passing test found = a passing test is expected but was not found from the source data.


MFD Motorfuel Dispensing Forms

No Forms Found