Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 7045432
Status: Active
Facility Name: E-Town Riverport Express
Address: 100 1st St.
Elizabethtown, IL 62931
County: Hardin
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y000913
Green Tag Issue Date: 7/6/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: Pat Joyner
Owner Address: P.O. Box 142
Elizabethtown, IL 62931
Owner Status: Current Owner
Purchase Date:
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 7/16/2025

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 7/6/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0036972 Joyner, Pat Current Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violations (Current)

NOV Number: E0020250567 (Pending)    Issue Date: 3/5/2025    Expiration Date: 5/4/2025    View NOV Form

Tanks Violation
Facility Annual Emergency Stop Inspection not completed or inspection report not available. - Report not available.
1 Dispensers - hoses cracked, split or worn and require replacement - Regular unleaded hoses require replacement.
3 Line leak detection equipment in alarm or failed test, must repair or replace. - STP sump sensor failed testing. Replacement must be submitted to OSFM (like -for like).
Facility Missing copies of 30 day Walkthrough Inspection Report. - Walkthrough not completed since July 2024.
Facility Missing copies of Annual Walkthrough Inspection Report. - Report not available.
Facility Missing copies of current testing certificates for operator training - No Class C certified employee on site.
Facility Missing list of designated Class A/B & C Operators - Update list.
1, 2, 3 Monthly line interstitial sensor records not available.
1, 2, 3 Piping interstitial must be open in all sumps
1, 2, 3 Required monthly tank interstitial sensor records not available.
1, 2, 3 Shear valve inspection report not completed (Required during Annual Walkthrough Inspection). - Report not available during inspection.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 12000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 12/3/2013 Abandoned Material:
Current Age: 11 Abandoned Date:
Install Date: 9/11/2013 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Composite Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 12/11/2024 12/11/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 12/11/2024 12/11/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 12/11/2024 12/11/2025
Overfill Prev Device Overfill Drop Tube Valve 12/11/2024 12/11/2027
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping STP/Tanktop Sump containment FRP 12/11/2024 12/11/2027
Leak Detect - Piping Sump Sensor with positive shutdown 12/11/2024 12/11/2025
Spill Contain Device Single Wall Spill Bucket 12/11/2024 12/11/2027
Tank Composite Double Wall Modern Welding Glasteel II N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 12/11/2024



Tank Number 2

Capacity: 6000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 12/3/2013 Abandoned Material:
Current Age: 11 Abandoned Date:
Install Date: 9/11/2013 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Composite Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 12/11/2024 12/11/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 12/11/2024 12/11/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 12/11/2024 12/11/2025
Overfill Prev Device Overfill Drop Tube Valve 12/11/2024 12/11/2027
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping STP/Tanktop Sump containment FRP 12/11/2024 12/11/2027
Leak Detect - Piping Sump Sensor with positive shutdown 12/11/2024 12/11/2025
Spill Contain Device Single Wall Spill Bucket 12/11/2024 12/11/2027
Tank Composite Double Wall Modern Welding Glasteel II N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 12/11/2024



Tank Number 3

Capacity: 6000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 12/3/2013 Abandoned Material:
Current Age: 11 Abandoned Date:
Install Date: 9/11/2013 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Composite Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 12/11/2024 12/11/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 12/11/2024 12/11/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 12/11/2024 12/11/2025
Overfill Prev Device Overfill Drop Tube Valve 12/11/2024 12/11/2027
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping STP/Tanktop Sump containment FRP 12/11/2024 12/11/2027
Leak Detect - Piping Sump Sensor with positive shutdown 12/11/2023 12/11/2024
Leak Detect - Piping Sump Sensor with positive shutdown 3/6/2025 3/6/2026
Spill Contain Device Single Wall Spill Bucket 12/11/2024 12/11/2027
Tank Composite Double Wall Modern Welding Glasteel II N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 12/11/2024

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 12/11/2024 12/11/2027
Leak Detect - Piping Sump Sensor with positive shutdown 12/11/2024 12/11/2025



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 12/11/2024 12/11/2027
Leak Detect - Piping Sump Sensor with positive shutdown 12/11/2024 12/11/2025

MFD Motorfuel Dispensing Forms

No Forms Found