Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 7044864
Status: Active
Facility Name: Ninkasi Beverage Group, LLC d/b/a Marketplace - Shell
Address: 2301 Reed Station Parkway Carbondale, IL 62901
County: Jackson
Property Parcel: 15-13-126-006
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y004245
Green Tag Issue Date: 9/5/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: Ninkasi Investment, LLC
Owner Address: 514 S. Illinois Ave. Carbondale, IL 62901
Owner Status: Current Owner
Purchase Date: 9/7/2018
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 8/22/2026

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 5/24/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0039280 Ninkasi Investment, LLC Current Owner 9/7/2018
U0036053 HBA Development Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020252091 (Referred to Legal)    Issue Date: 8/14/2025    Expiration Date: 10/13/2025    View NOV Form

Tanks Violations
1, 2, 3, 4 Piping sump tested triennially using low level positive shut off option. Sump does not meet low level test requirements. See remarks. Perform standard hydrostatic test on sump. - STP sumps require standard hydrostatic test due to the violations. Dispensers 1/2 3/4, 5/6, 7/8, 11/12, 15/16,(sumps are cracked).
1, 2, 4 Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. - STP sumps are full of liquid. Dispenser sumps are cracked and piping backfill has migrated into sumps, repair containments and perform a standard hydrostatic test following the repairs.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 20000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 7/12/2011 Abandoned Material:
Current Age: 14 Abandoned Date:
Install Date: 7/8/2011 Red Tag Issue Date: 11/12/2025
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 2/4/2025 2/4/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 with CSLD 2/4/2025 2/4/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 2/4/2025 2/4/2026
Overfill Prev Device Overfill Drop Tube Valve 2/4/2025 2/4/2028
Piping Fiberglass Double Wall Ameron N/A N/A
Piping Single Wall STP/Tanktop Sump 2/4/2025 2/4/2028
Leak Detect - Piping Sump Sensor with positive shutdown 2/4/2025 2/4/2026
Spill Contain Device Single Wall Spill Bucket 2/4/2025 2/4/2028
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Precision Test (Piping) Pass 2/4/2025



Tank Number 2

Capacity: 6000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 7/12/2011 Abandoned Material:
Current Age: 14 Abandoned Date:
Install Date: 7/8/2011 Red Tag Issue Date: 11/12/2025
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 2/4/2025 2/4/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 with CSLD 2/4/2025 2/4/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 2/4/2025 2/4/2026
Overfill Prev Device Overfill Drop Tube Valve 2/4/2025 2/4/2028
Piping Fiberglass Double Wall Ameron N/A N/A
Piping Single Wall STP/Tanktop Sump 2/4/2025 2/4/2028
Leak Detect - Piping Sump Sensor with positive shutdown 2/4/2025 2/4/2026
Spill Contain Device Single Wall Spill Bucket 2/4/2025 2/4/2028
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Precision Test (Piping) Pass 2/4/2025



Tank Number 3

Capacity: 8000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 7/12/2011 Abandoned Material:
Current Age: 14 Abandoned Date:
Install Date: 7/8/2011 Red Tag Issue Date: 11/12/2025
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 2/4/2025 2/4/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 with CSLD 2/4/2025 2/4/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 2/4/2025 2/4/2026
Overfill Prev Device Overfill Drop Tube Valve 2/4/2025 2/4/2028
Piping Fiberglass Double Wall Ameron N/A N/A
Piping Single Wall STP/Tanktop Sump 2/4/2025 2/4/2028
Leak Detect - Piping Sump Sensor with positive shutdown 2/4/2025 2/4/2026
Spill Contain Device Single Wall Spill Bucket 2/4/2025 2/4/2028
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Precision Test (Piping) Pass 2/4/2025



Tank Number 4

Capacity: 6000 Petroleum Use:
Product: Gasoline - Non Ethanol CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 7/12/2011 Abandoned Material:
Current Age: 14 Abandoned Date:
Install Date: 7/8/2011 Red Tag Issue Date: 11/12/2025
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 2/4/2025 2/4/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 with CSLD 2/4/2025 2/4/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 2/4/2025 2/4/2026
Overfill Prev Device Overfill Drop Tube Valve 2/4/2025 2/4/2028
Piping Fiberglass Double Wall Ameron N/A N/A
Piping Single Wall STP/Tanktop Sump 2/4/2025 2/4/2028
Leak Detect - Piping Sump Sensor with positive shutdown 2/4/2025 2/4/2026
Spill Contain Device Single Wall Spill Bucket 2/4/2025 2/4/2028
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Precision Test (Piping) Pass 2/4/2025

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 2/4/2025 2/4/2028
Leak Detect - Piping Sump Sensor with positive shutdown 2/4/2025 2/4/2026



Name\ID 11/12

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 2/4/2025 2/4/2028
Leak Detect - Piping Sump Sensor with positive shutdown 2/4/2025 2/4/2026



Name\ID 13/14

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 2/4/2025 2/4/2028
Leak Detect - Piping Sump Sensor with positive shutdown 2/4/2025 2/4/2026



Name\ID 15/16

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 2/4/2025 2/4/2028
Leak Detect - Piping Sump Sensor with positive shutdown 2/4/2025 2/4/2026



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 2/4/2025 2/4/2028
Leak Detect - Piping Sump Sensor with positive shutdown 2/4/2025 2/4/2026



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 2/4/2025 2/4/2028
Leak Detect - Piping Sump Sensor with positive shutdown 2/4/2025 2/4/2026



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 2/4/2025 2/4/2028
Leak Detect - Piping Sump Sensor with positive shutdown 2/4/2025 2/4/2026



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 2/4/2025 2/4/2028
Leak Detect - Piping Sump Sensor with positive shutdown 2/4/2025 2/4/2026

MFD Motorfuel Dispensing Forms

No Forms Found