Deficiencies (Current)
NOV Number:
E0020241396
(Pending)
Issue Date:
5/21/2024
Expiration Date:
7/20/2024
View NOV Form
Tanks |
Deficiency |
Facility |
Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable |
Facility |
Fire Extinguishers - Past due for annual testing |
Facility |
Miscellaneous - Remove flammable liquid, wood chips or mulch located within 10' of dispensers |
NOV Number:
E0020241397
(Pending)
Issue Date:
5/21/2024
Expiration Date:
7/20/2024
View NOV Form
Tanks |
Deficiency |
1, 3 |
Dispensers - hoses cracked, split or worn and require replacement |
1, 2, 3 |
Line interstitial sensors have been raised and rendered inoperational. - STP sump sensors must be located on the bottom in the lowest point of the containment. Remove liquid and repair sump lids to properly seal STP sumps. |
1, 2, 3 |
Triennial spill prevention equipment testing not completed. |
1, 2, 3 |
Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. - STP sump lids do not seal correctly, repair/replace. |