| 1, 3 |
Line interstitial sensors have been raised and rendered inoperational. - Dispenser sumps, #7/8, 5/6, 3/4 |
| 3 |
Line leak detection equipment in alarm or failed test, must repair or replace. - Premium STP (L7) Alarm; sump is full of water. |
| Facility |
Missing copies of 30 day Walkthrough Inspection Report. - 30 day Walkthrough inspection not completed by A/B Operator since June 2026. |
| Facility |
Missing copies of current testing certificates for operator training - Dawn Piercy, C Operator Certificate is expired. |
| Facility |
Operator training course taken not approved by the Office of the Illinois State Fire Marshal - 360Training.com is not approved by OSFM. |
| 1, 2, 3 |
Piping interstitial must be open in all sumps - Dispensers 7/8, 5/6, 3/4, 1/2, Regular unleaded North STP sump, Premium STP sump. |
| 3 |
Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. - Premium STP sump is full of water. |