| 4 |
Dispensers - hoses cracked, split or worn and require replacement - Dispenser #1 whip hose/ REG. hose, #2 whip hose/ REG. hose, #3 whip hose/ REG. hose, #4 whip hose/ REG. hose, #5 whip hose/ REG. hose, #6 whip hose/ REG. hose. |
| 6 |
Line interstitial sensors have been raised and rendered inoperational. - Dispenser #7/8 M sensor has been raised, needs to lowered to the bottom of the UDC. |
| Facility |
Missing copies of 30 day Walkthrough Inspection Report. - Inspection reports not completed. |
| Facility |
Missing list of designated Class A/B & C Operators |
| 4, 6 |
Monthly line interstitial sensor records not available. |
| 4, 6 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. |
| 4, 6 |
Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. - Tank #6 STP sensor in "Fuel Alarm". |