Notice of Violations (Current)
NOV Number:
E0020250974
(Pending)
Issue Date:
4/10/2025
Expiration Date:
6/9/2025
View NOV Form
Tanks |
Violation |
1, 2 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. |
2 |
Water in containment without required interstitial sensors - install cathodic protection on all exposed steel. - Diesel tank STP sump requires repair to prevent water ingress or install cathodic protection. |
NOV Number:
E0020250976
(Pending)
Issue Date:
4/10/2025
Expiration Date:
6/9/2025
View NOV Form
Tanks |
Violation |
Facility |
Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable |