Notice of Violatlions (Current)
NOV Number:
E0020251485
(Pending)
Issue Date:
6/10/2025
Expiration Date:
8/9/2025
View NOV Form
Tanks |
Violations |
1, 2 |
Line interstitial sensor functional test not accomplished (Required annually). - All piping sumps and sensors are regulated due to multiple upgrades. |
Facility |
Miscellaneous - Emergency stop at all control stations shall be conspicuously marked and readily accessible to the attendant. Each emergency stop shall be identified by a sign on all-weather materials stating "EMERGENCY STOP" in 2 inch red capital letters. (Section 175.210) |
Facility |
Missing copies of 30 day Walkthrough Inspection Report. |
1, 2 |
Piping interstitial must be open in all sumps |
1, 2 |
Triennial testing for qualifying piping containment sump not completed (Required every 3 years). - All piping sumps and sensors are regulated due to multiple upgrades. |
NOV Number:
E0020251486
(Pending)
Issue Date:
6/10/2025
Expiration Date:
8/9/2025
View NOV Form
Tanks |
Violations |
Facility |
Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable |
Facility |
Miscellaneous - All dispensing units shall be readily visible from the control station without assistive devices. |