Notice of Violatlions (Current)
NOV Number:
E0020252173
(Pending)
Issue Date:
8/21/2025
Expiration Date:
10/20/2025
View NOV Form
Tanks |
Violations |
7 |
Line interstitial sensors have been raised and rendered inoperational. |
9 |
Miscellaneous - All equipment shall be kept in good operating condition at all times. Repair/replace double wall piping. |
7 |
Piping sump tested triennially using low level positive shut off option. Sump does not meet low level test requirements. See remarks. Perform standard hydrostatic test on sump. - STP sump contains liquid and sensor is raised out of liquid. |
7 |
Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. |