Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 7032182
Status: Active
Facility Name: Four Way Quick Stop, LLC
Address: 200 North Chestnut De Soto, IL 62924
County: Jackson
Property Parcel: 10-20-230-015
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Z001801
Green Tag Issue Date: 9/25/2024
Green Tag Expire Date: 12/31/2026
MFD Type: N/A

Owner Details

Owner Name: Nick Investment of IL Corporation
Owner Address: 200 N Chestnut De Soto, IL 62924
Owner Status: Current Owner
Purchase Date: 11/20/2023
Type of Financial Responsibility: Designated Savings Account
Financial Responsibility Reporting Due Date: 12/3/2026

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0041298 Nick Investment of IL Corporation Current Owner 11/20/2023
U0034718 Parsons, Tim & Melissa Former Owner 2/15/2007
U0021667 Gene Clark Former Owner 1/7/1994

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violations (Current)

NOV Number: E0020262140 (Pending)    Issue Date: 8/24/2026    Expiration Date: 10/23/2026    View NOV Form

Tanks Violations
1, 2 Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - Protective covers for STPs and tank risers are required to be repaired at grade.
Facility Facility Operation and Maintenance Plan not completed or available. - Template left onsite to be completed by Owner/ and A/B Operator.
Facility Missing copies of 30 day Walkthrough Inspection Report. - Template left onsite to be completed by Owner/ and A/B Operator.
Facility Missing copies of current testing certificates for operator training - No Class A/B or Class C certificates available.
Facility Missing copy of emergency instructions or emergency procedures plan - Template left onsite to be completed by Owner/ and A/B Operator.
Facility Missing list of designated Class A/B & C Operators - Template left onsite to be completed by Owner/ and A/B Operator.
2 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 10000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 1/20/1994 Abandoned Material:
Current Age: 32 Abandoned Date:
Install Date: 10/13/1993 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 12/22/1993

Equipment Information

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 11/7/2025 11/7/2028
Corrosion Prot - Piping Fiberglass Non-Corrosive Not applicable Not applicable
Corrosion Prot - Tank STIP3 Cathodic Protection with Dielectric Coating 11/7/2025 11/7/2028
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 11/7/2025 11/7/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 11/7/2025 11/7/2026
Overfill Prev Device Ball Float Vent Valve OPW 53VM 9/18/2024 9/18/2027
Piping Fiberglass Single Wall Piping Not applicable Not applicable
Piping Not Installed STP/Tanktop Sump Not applicable Not applicable
Spill Contain Device Single Wall Spill Bucket 9/18/2024 9/18/2027
Tank STIP3 Single Wall Not applicable Not applicable

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test (Piping) Pass 11/7/2025
Tank STIP3 Single Wall Precision Test (Tank) Pass 9/20/2024



Tank Number 2

Capacity: 4000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 1/20/1994 Abandoned Material:
Current Age: 32 Abandoned Date:
Install Date: 10/13/1993 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 12/22/1993

Equipment Information

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 11/7/2025 11/7/2028
Corrosion Prot - Piping Fiberglass Non-Corrosive Not applicable Not applicable
Corrosion Prot - Tank STIP3 Cathodic Protection with Dielectric Coating 11/7/2025 11/7/2028
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 11/7/2025 11/7/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 11/7/2025 11/7/2026
Overfill Prev Device Ball Float Vent Valve OPW 53VM 9/18/2024 9/18/2027
Piping Fiberglass Single Wall Piping Not applicable Not applicable
Piping Not Installed STP/Tanktop Sump Not applicable Not applicable
Spill Contain Device Double Wall Spill Bucket 9/18/2024 9/18/2027
Tank STIP3 Single Wall Not applicable Not applicable

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test (Piping) Pass 11/7/2025
Tank STIP3 Single Wall Precision Test (Tank) Pass 9/20/2024



Tank Number 3

Capacity: 4000 Petroleum Use:
Product: Gasoline - Mid-grade CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 1/20/1994 Abandoned Material:
Current Age: 32 Abandoned Date:
Install Date: 10/13/1993 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 12/22/1993

Equipment Information

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 11/7/2025 11/7/2028
Corrosion Prot - Piping Fiberglass Non-Corrosive Not applicable Not applicable
Corrosion Prot - Tank STIP3 Cathodic Protection with Dielectric Coating 11/7/2025 11/7/2028
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 11/7/2025 11/7/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 11/7/2025 11/7/2026
Overfill Prev Device Ball Float Vent Valve OPW 53VM 9/18/2024 9/18/2027
Piping Fiberglass Single Wall Piping Not applicable Not applicable
Piping Not Installed STP/Tanktop Sump Not applicable Not applicable
Spill Contain Device Single Wall Spill Bucket 9/18/2024 9/18/2027
Tank STIP3 Single Wall Not applicable Not applicable

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test (Piping) Pass 11/7/2025
Tank STIP3 Single Wall Precision Test (Tank) Pass 9/20/2024



Tank Number 4

Capacity: 4000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 1/20/1994 Abandoned Material:
Current Age: 32 Abandoned Date:
Install Date: 10/13/1993 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 12/22/1993

Equipment Information

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 11/7/2025 11/7/2028
Corrosion Prot - Piping Fiberglass Non-Corrosive Not applicable Not applicable
Corrosion Prot - Tank STIP3 Cathodic Protection with Dielectric Coating 11/7/2025 11/7/2028
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 11/7/2025 11/7/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 11/7/2025 11/7/2026
Overfill Prev Device Ball Float Vent Valve OPW 53VM 9/18/2024 9/18/2027
Piping Fiberglass Single Wall Piping Not applicable Not applicable
Piping Not Installed STP/Tanktop Sump Not applicable Not applicable
Spill Contain Device Single Wall Spill Bucket 9/18/2024 9/18/2027
Tank STIP3 Single Wall Not applicable Not applicable

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test (Piping) Pass 11/7/2025
Tank STIP3 Single Wall Precision Test (Tank) Pass 9/20/2024

Failed test = the latest test has failed.

Not applicable = a test does not apply to this equipment type or configuration.

No passing test found = a passing test is expected but was not found from the source data.


Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump Not applicable Not applicable



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump Not applicable Not applicable



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump Not applicable Not applicable
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required Not applicable Not applicable

Failed test = the latest test has failed.

Not applicable = a test does not apply to this equipment type or configuration.

No passing test found = a passing test is expected but was not found from the source data.


MFD Motorfuel Dispensing Forms