Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 7029255
Status: Active
Facility Name: Rock Bottom Liquor (formerly Hucks #257)
Address: 1109 West Main Carmi, IL 62821
County: White
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y000959
Green Tag Issue Date: 9/20/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: K & N 2017, Inc.
Owner Address: 1109 W. Main Street Carmi, IL 628211425
Owner Status: Current Owner
Purchase Date: 5/17/2017
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 8/26/2026

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 9/20/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0038777 K & N 2017, Inc. Current Owner 5/17/2017
U0009763 Martin & Bayley, Inc. Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020252206 (Pending)    Issue Date: 8/26/2025    Expiration Date: 10/25/2025    View NOV Form

Tanks Violations
Facility Code complying instruction/warning signs are not properly mounted at each dispenser island - Minimum Signage. Signs shall be provided that are clearly visible to all self-service customers. The signs shall be made of all-weather material and the lettering shall be not less than ? inch high. The top of the signs shall be mounted no higher than 10 feet above grade, or at a height approved by OSFM, and shall include the following wording, at a minimum: 1) "Warning"; 2) "Stop Engine"; 3) "No Smoking"; 4) "Persons fueling vehicles shall remain with their vehicle, at the nozzle, while fueling is in progress"; 5) "It is unlawful and dangerous for anyone to dispense gasoline into unapproved containers".
Facility Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
95-2501 Eligible 2/29/1996 3/21/1996 $10,000
Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 10000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 10/21/1991 Abandoned Material:
Current Age: 33 Abandoned Date:
Install Date: 7/1/1991 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 12/1/1991

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 8/21/2023 8/21/2026
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 8/26/2025 8/26/2026
Leak Detect - Tank Automatic Tank Gauging Gilbarco EMC with CSLD 8/26/2025 8/26/2026
Overfill Prev Device Overfill Drop Tube Valve 8/16/2024 8/16/2027
Piping Fiberglass Single Wall Piping N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A
Spill Contain Device Single Wall Spill Bucket 8/16/2024 8/16/2027
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test (Piping) Pass 8/26/2025



Tank Number 2

Capacity: 10000 Petroleum Use:
Product: Gasoline - Mid-grade CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 10/21/1991 Abandoned Material:
Current Age: 33 Abandoned Date:
Install Date: 7/1/1991 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 12/1/1991

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 8/21/2023 8/21/2026
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 8/26/2025 8/26/2026
Leak Detect - Tank Automatic Tank Gauging Gilbarco EMC with CSLD 8/26/2025 8/26/2026
Overfill Prev Device Overfill Drop Tube Valve 8/16/2024 8/16/2027
Piping Fiberglass Single Wall Piping N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A
Spill Contain Device Single Wall Spill Bucket 8/16/2024 8/16/2027
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test (Piping) Pass 8/26/2025



Tank Number 3

Capacity: 10000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 10/21/1991 Abandoned Material:
Current Age: 33 Abandoned Date:
Install Date: 7/1/1991 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 12/1/1991

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 8/21/2023 8/21/2026
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 8/26/2025 8/26/2026
Leak Detect - Tank Automatic Tank Gauging Gilbarco EMC with CSLD 8/26/2025 8/26/2026
Overfill Prev Device Overfill Drop Tube Valve 8/16/2024 8/16/2027
Piping Fiberglass Single Wall Piping N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A
Spill Contain Device Single Wall Spill Bucket 8/16/2024 8/16/2027
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test (Piping) Pass 8/26/2025

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A

MFD Motorfuel Dispensing Forms