Owner Summary
Click for Facility/Tank Ownership history
| Owner Number |
Owner Name |
Owner Status |
Purchase Date |
| U0038811 |
Varahi, Inc. |
Current Owner |
4/4/2017 |
| U0037407 |
Black Gold Ventures Indiana, LLC |
Former Owner |
7/15/2014 |
| U0014784 |
Swifty Oil Company, Inc. |
Former Owner |
11/11/1986 |
| U0021101 |
Kerr Mcgee Refining Corp |
Former Owner |
|
Notice of Violations (Current)
NOV Number:
E0020262148
(Pending)
Issue Date:
8/25/2026
Expiration Date:
10/24/2026
View NOV Form
| Tanks |
Violations |
| 1, 2, 3 |
Miscellaneous - Dispenser #1 REG. whip hose/ REG hose, #2 REG. whip hose/ REG hose, #3 REG. whip hose/ REG hose, #4 REG. whip hose/ REG hose, Diesel hose |
| 1, 2 |
Water in containment without required sensors – install cathodic protection on all exposed steel piping or make containment watertight. By 10/13/28, all containments must be watertight and any CP installed in containments must be removed. - UDC sump needs water removed. |
IEMA Numbers Associated with the Facility
No IEMA Numbers Found
LUST
Fund Eligibility and Deductibility Determinations
| IEMA Number |
Status |
OSFM Received Date |
OSFM Response Date |
Deductible |
Letter |
| 13-1262 |
Eligible |
5/5/2014
|
5/29/2014
|
$5,000
|
|
Tank Number 1
| Capacity: |
10152 |
|
Petroleum Use: |
|
| Product: |
Gasoline - Regular |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
1/6/1987 |
|
Abandoned Material: |
|
| Current Age: |
39 |
|
Abandoned Date: |
|
| Install Date: |
11/11/1986 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
11/11/1986 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Sacrificial Anode Flex Connector |
8/21/2025 |
8/21/2028 |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
STIP3 Cathodic Protection with Dielectric Coating |
8/21/2025 |
8/21/2028 |
|
Leak Detect - Piping
|
Electronic Pressurized Line Leak Detection |
8/12/2026 |
8/12/2027 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 350 |
8/12/2026 |
8/12/2027 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
8/21/2025 |
8/21/2028 |
|
Piping
|
Fiberglass Double Wall Ameron |
Not applicable |
Not applicable |
|
Piping
|
Fiberglass Single Wall Piping |
Not applicable |
Not applicable |
|
Piping
|
Not Installed STP/Tanktop Sump |
Not applicable |
Not applicable |
|
Spill Contain Device
|
Single Wall Spill Bucket |
8/21/2025 |
8/21/2028 |
|
Tank
|
STIP3 Single Wall |
Not applicable |
Not applicable |
|
Vent, Riser, Fill Piping
|
Steel risers |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Fiberglass Double Wall Ameron
|
Precision Test (Piping)
|
Pass
|
8/29/2024
|
|
Piping
|
Fiberglass Single Wall Piping
|
Precision Test (Piping)
|
Pass
|
8/29/2024
|
|
Tank
|
STIP3 Single Wall
|
Precision Test (Tank)
|
Pass
|
8/29/2024
|
Tank Number 2
| Capacity: |
10152 |
|
Petroleum Use: |
|
| Product: |
Gasoline - Premium |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
1/6/1987 |
|
Abandoned Material: |
|
| Current Age: |
39 |
|
Abandoned Date: |
|
| Install Date: |
11/11/1986 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
11/11/1986 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Sacrificial Anode Flex Connector |
8/21/2025 |
8/21/2028 |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
STIP3 Cathodic Protection with Dielectric Coating |
8/21/2025 |
8/21/2028 |
|
Leak Detect - Piping
|
Electronic Pressurized Line Leak Detection |
8/12/2026 |
8/12/2027 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 350 |
8/12/2026 |
8/12/2027 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
8/21/2025 |
8/21/2028 |
|
Piping
|
Fiberglass Double Wall Ameron |
Not applicable |
Not applicable |
|
Piping
|
Fiberglass Single Wall Piping |
Not applicable |
Not applicable |
|
Piping
|
Not Installed STP/Tanktop Sump |
Not applicable |
Not applicable |
|
Spill Contain Device
|
Single Wall Spill Bucket |
8/21/2025 |
8/21/2028 |
|
Tank
|
STIP3 Single Wall |
Not applicable |
Not applicable |
|
Vent, Riser, Fill Piping
|
Steel risers |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Fiberglass Double Wall Ameron
|
Precision Test (Piping)
|
Pass
|
8/29/2024
|
|
Piping
|
Fiberglass Single Wall Piping
|
Precision Test (Piping)
|
Pass
|
8/29/2024
|
|
Tank
|
STIP3 Single Wall
|
Precision Test (Tank)
|
Pass
|
8/29/2024
|
Tank Number 3
| Capacity: |
10152 |
|
Petroleum Use: |
|
| Product: |
B-11 |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
1/6/1987 |
|
Abandoned Material: |
|
| Current Age: |
39 |
|
Abandoned Date: |
|
| Install Date: |
11/11/1986 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
11/11/1986 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Sacrificial Anode Flex Connector |
8/21/2025 |
8/21/2028 |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
STIP3 Cathodic Protection with Dielectric Coating |
8/21/2025 |
8/21/2028 |
|
Leak Detect - Piping
|
Electronic Pressurized Line Leak Detection |
8/12/2026 |
8/12/2027 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 350 |
8/12/2026 |
8/12/2027 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
8/21/2025 |
8/21/2028 |
|
Piping
|
Fiberglass Double Wall Ameron |
Not applicable |
Not applicable |
|
Piping
|
Fiberglass Single Wall Piping |
Not applicable |
Not applicable |
|
Piping
|
Not Installed STP/Tanktop Sump |
Not applicable |
Not applicable |
|
Spill Contain Device
|
Single Wall Spill Bucket |
8/21/2025 |
8/21/2028 |
|
Tank
|
STIP3 Single Wall |
Not applicable |
Not applicable |
|
Vent, Riser, Fill Piping
|
Steel risers |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Fiberglass Double Wall Ameron
|
Precision Test (Piping)
|
Pass
|
8/29/2024
|
|
Piping
|
Fiberglass Single Wall Piping
|
Precision Test (Piping)
|
Pass
|
8/29/2024
|
|
Tank
|
STIP3 Single Wall
|
Precision Test (Tank)
|
Pass
|
8/29/2024
|
Tank Number 4
| Capacity: |
6016 |
|
Petroleum Use: |
|
| Product: |
Kerosene |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
1/6/1987 |
|
Abandoned Material: |
|
| Current Age: |
39 |
|
Abandoned Date: |
|
| Install Date: |
11/11/1986 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
11/11/1986 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Sacrificial Anode Flex Connector |
8/21/2025 |
8/21/2028 |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
STIP3 Cathodic Protection with Dielectric Coating |
8/21/2025 |
8/21/2028 |
|
Leak Detect - Piping
|
Electronic Pressurized Line Leak Detection |
8/12/2026 |
8/12/2027 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 350 |
8/12/2026 |
8/12/2027 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
8/21/2025 |
8/21/2028 |
|
Piping
|
Fiberglass Single Wall Piping |
Not applicable |
Not applicable |
|
Piping
|
Not Installed STP/Tanktop Sump |
Not applicable |
Not applicable |
|
Spill Contain Device
|
Single Wall Spill Bucket |
8/21/2025 |
8/21/2028 |
|
Tank
|
STIP3 Single Wall |
Not applicable |
Not applicable |
|
Vent, Riser, Fill Piping
|
Steel risers |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Fiberglass Single Wall Piping
|
Precision Test (Piping)
|
Pass
|
8/29/2024
|
|
Tank
|
STIP3 Single Wall
|
Precision Test (Tank)
|
Pass
|
8/29/2024
|
Tank Number 5
| Capacity: |
10000 |
|
Petroleum Use: |
|
| Product: |
Gasoline |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Exempt |
|
Removed Date: |
10/28/1986 |
|
OSFM
First Notify Date: |
3/3/1986 |
|
Abandoned Material: |
|
| Current Age: |
20 |
|
Abandoned Date: |
|
| Install Date: |
1/1/1966 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
1/1/1986 |
|
Fee Due: |
|
| Product Date: |
|
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 6
| Capacity: |
6000 |
|
Petroleum Use: |
|
| Product: |
Gasoline |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Exempt |
|
Removed Date: |
10/28/1986 |
|
OSFM
First Notify Date: |
3/3/1986 |
|
Abandoned Material: |
|
| Current Age: |
20 |
|
Abandoned Date: |
|
| Install Date: |
1/1/1966 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
1/1/1986 |
|
Fee Due: |
|
| Product Date: |
|
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 7
| Capacity: |
500 |
|
Petroleum Use: |
|
| Product: |
Used Oil |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Exempt |
|
Removed Date: |
10/28/1986 |
|
OSFM
First Notify Date: |
3/3/1986 |
|
Abandoned Material: |
|
| Current Age: |
20 |
|
Abandoned Date: |
|
| Install Date: |
1/1/1966 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
10/28/1986 |
|
Fee Due: |
|
| Product Date: |
|
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
Dispenser Information
Name\ID 1/2
| Status: |
Active |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Single Wall UDC Sump |
Not applicable
|
Not applicable
|
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated Not Required |
Not applicable
|
Not applicable
|
Name\ID 3/4
| Status: |
Active |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Single Wall UDC Sump |
Not applicable
|
Not applicable
|
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated Not Required |
Not applicable
|
Not applicable
|
Name\ID K-1
| Status: |
Active |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Not Installed UDC Sump |
Not applicable
|
Not applicable
|
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
MFD
Motorfuel Dispensing Forms
No Forms Found