Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 7023226
Status: Active
Facility Name: ROC 1 Stop #12
Address: 201 North 1st Street
Vienna, IL 62995
County: Johnson
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y000924
Green Tag Issue Date: 5/5/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: Russell Oil Company
Owner Address: 200 E. Main
Galatia, IL 62935
Owner Status: Current Owner
Purchase Date: 9/17/2010
Type of Financial Responsibility: Certificate of Deposit
Financial Responsibility Reporting Due Date: 1/14/2026

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 5/5/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0013266 Russell Oil Company Current Owner 9/17/2010
U0034044 Alchemist USA, LLC Former Owner 2/21/2007
U0015667 Veach Oil Company Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violations (Current)

NOV Number: E0020250758 (Pending)    Issue Date: 3/24/2025    Expiration Date: 5/23/2025    View NOV Form

Tanks Violation
Facility Annual Emergency Stop Inspection not completed or inspection report not available.
7, 8, 9 Line interstitial sensors have been raised and rendered inoperational. - North Gasoline STP Diesel STP, Dispensers 1/2, 7/8.
7 Line leak detection equipment in alarm or failed test, must repair or replace. - South Gasloline STP sump in alarm, repair/replace.
Facility Missing copies of Annual Walkthrough Inspection Report.
Facility Missing list of designated Class A/B & C Operators
7, 8, 9 Monthly line interstitial sensor records not available.
9 Required monthly tank interstitial sensor records not available.
7, 8, 9 Required monthly tank leak test records not available.
7, 8, 9 Shear valve inspection report not completed (Required during Annual Walkthrough Inspection).
9 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
10-1296 1/10/2011 Removal Log 01393-2010REM
10-1296 1/10/2011 Abandonment Log 00014-2011ABN

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
10-1296 Eligible 2/14/2011 2/25/2011 $5,000
Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 3000 Gasoline Abandoned in place Federal $0.00 01/10/2011 - ABN
2 2000 Diesel Fuel Removed Federal $0.00 01/10/2011 - REM
3 1000 Kerosene Removed Federal $0.00 11/05/1990 - REM
4 1000 Kerosene Removed Federal $0.00 01/10/2011 - REM
5 8000 Gasoline Removed Federal $0.00 07/19/2000 - REM
6 4000 Gasoline Removed Federal $0.00 07/19/2000 - REM
7 8000 Gasoline - Regular Currently in use Federal $0.00
8 4000 Gasoline - Regular Currently in use Federal $0.00
9 4000 Diesel Fuel Currently in use Federal
10 550 Gasoline Removed Federal $0.00 01/10/2011 - REM

Dispenser Information

Name\ID Status
1/2 Active
3/4 Active
5/6 Active
7/8 Active

MFD Motorfuel Dispensing Forms

No Forms Found