Notice of Violations (Current)
NOV Number:
E0020250505
(Pending)
Issue Date:
2/27/2025
Expiration Date:
4/28/2025
View NOV Form
Tanks |
Violation |
4, 5, 6, 7 |
Dispensers - hoses cracked, split or worn and require replacement - Diesel hose on 4. Gas hose on 3. Gas whip hoses on 4 and 8. |
5, 6, 7 |
Dispensers - the following hoses or breakaways are missing or actively leaking and require immediate replacement (bagged at inspection) |
6 |
Open electrical conduit or junction boxes. - Tank probe junction box/conduit is corroded and broken off. |
4, 5, 6, 7 |
Piping interstitial must be open in all sumps |
4, 5, 6, 7 |
Vent cap(s) missing. - One vent cap missing, unable to verify which product is missing the vent cap. |
NOV Number:
E0020250506
(Pending)
Issue Date:
2/27/2025
Expiration Date:
4/28/2025
View NOV Form
Tanks |
Violation |
Facility |
Miscellaneous - Conspicuously marked and easily accessible emergency stops must be provided at each facility and shall be located so that at least one emergency stop is at least 20 feet but not more than 100 feet from each dispenser. |