Notice of Violations (Current)
NOV Number:
E0020261444
(Pending)
Issue Date:
6/4/2026
Expiration Date:
8/3/2026
View NOV Form
| Tanks |
Violations |
| 4, 5, 6 |
Line interstitial sensors have been raised and rendered inoperational. - Dispenser sump sensors are raised off the bottom of the sump. |
| 4, 5 |
Miscellaneous - Actions Requiring a Permit. A permit is required to do any of the following to USTs: Upgrade Automatic Tank Gauging |
| 5 |
Miscellaneous - Install or replace lockable probe riser caps. |
| 6 |
Miscellaneous - Actions Requiring a Permit. A permit is required to do any of the following to USTs: Upgrade Automatic Tank Gauging |
| 4, 5, 6 |
Piping interstitial must be open in all sumps |