4 |
Dispensers - hoses cracked, split or worn and require replacement |
4, 5, 6 |
Line interstitial sensors have been raised and rendered inoperational. - All STP sumps sensors raised. Dispensers 5/6, 3/4, 1/2 |
4, 5, 6 |
Piping interstitial must be open in all sumps |
4, 5, 6 |
Piping sump tested triennially using low level positive shut off option. Sump does not meet low level test requirements. See remarks. Perform standard hydrostatic test on sump. - Sensors raised, and some have liquid. |
4, 5, 6 |
Shear valve(s) not in proper working order. - Shear valve will not close. |