Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 7021609
Status: Inactive
Facility Name: Maharajswami 943 Corp. d/b/a Clay City Citgo
Address: 943 S. Main Street Route 50 & Clay City Road Clay City, IL 62824
County: Clay
Property Parcel: 12-19-400-017
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y000072
Green Tag Issue Date: 6/5/2023
Green Tag Expire Date: 11/20/2025
MFD Type: N/A

Owner Details

Owner Name: Ambemata Properties, LLC
Owner Address: 308 W. Delaware Street Fairfield, IL 62837
Owner Status: Current Owner
Purchase Date: 10/20/2021
Type of Financial Responsibility: Letter of Credit
Financial Responsibility Reporting Due Date: 6/8/2024

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0040385 Ambemata Properties, LLC Current Owner 10/20/2021
U0040005 Fuel Equity Partners, Inc. Former Owner 9/2/2020
U0008547 Knapp Oil Company, Inc. Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violations (Current)

NOV Number: E0020260481 (Pending)    Issue Date: 2/25/2026    Expiration Date: 4/26/2026   

Tanks Violations
Facility Financial responsibility must be reported yearly - Per 41 Ill. Adm. Code 176.220, tank owners/operators must submit an electronic Financial Responsibility Report form on an annual basis. Financial Responsibility must be maintained until the tank is removed or properly abandoned in place by a licensed UST decommissioning contractor. The form can be found at: https://webapps.sfm.illinois.gov/USTPortal/Forms/FinancialResponsibility.
1, 2, 3, 4 Remove tank(s) - Single-Walled, Over 30 Years Old and OOS Over One Year - Single walled tanks (1, 3 & 4) were taken out of service on 11/14/24, and are 44 years old. Per 175.810(e) single wall USTs must be removed, as they are now condemned. Tank #2 was previously abandoned in place on 3/14/19. Per 175.840(e), it states "when a UST is allowed to be abandoned-in-place, the abandoned-in-place UST shall be removed when the condition for issuing the abandonment no longer exists. The reason for abandonment, was tank #4 was located in the same tank bed as tanks 1, 3 & 4. Therefore since these tanks have to be removed, tank #2 will have to be removed too. Here is a link to the licensed UST Decommissioning contractors, that can perform UST tank removals: https://webapps.sfm.illinois.gov/ustsearch/ContractorSearch.aspx
Facility Submit Notification Form for Ownership Change - Per 41 Ill. Adm. Code 176.440 (g), a change of ownership information must be reported on an electronic Notification for Underground Storage Tank form, within 30 days of the change. According to the Clay County Property Tax Portal, this property was sold to you on 9/25/24. The Notification Form is available at: https://webapps.sfm.illinois.gov/USTPortal/NotificationForm.

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
19-0195 3/14/2019 Abandonment Log 00382-2019ABN

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
20190195 Eligible 4/18/2019 4/24/2019 $5,000 Letter
Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 8000 Petroleum Use: None
Product: Gasoline - Premium CERCLA Substance:
Status: Condemned Tank CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/6/1986 Abandoned Material:
Current Age: 44 Abandoned Date:
Install Date: 1/11/1982 Red Tag Issue Date: 11/14/2024
Last Used Date: 11/14/2024 Fee Due: $0.00
Product Date:

Equipment Information

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 12/15/2022 12/15/2025
Corrosion Prot - Piping Sacrificial Anode Flex Connector 12/15/2022 12/15/2025
Corrosion Prot - Piping Sacrificial Anode Flex Connector 12/15/2022 12/15/2025
Corrosion Prot - Piping Sacrificial Anode Flex Connector 12/15/2022 12/15/2025
Corrosion Prot - Piping Fiberglass Non-Corrosive Not applicable Not applicable
Corrosion Prot - Tank Lining Materials Internal Bridgeport Chemical Glass Armor GA 27P 5/2/2024 5/2/2029
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 5/16/2023 5/16/2024
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 Plus with CSLD 5/16/2023 5/16/2024
Overfill Prev Device Overfill Drop Tube Valve 5/16/2023 5/16/2026
Piping Fiberglass Single Wall Piping Not applicable Not applicable
Piping Not Installed STP/Tanktop Sump Not applicable Not applicable
Spill Contain Device Single Wall Spill Bucket 5/16/2023 5/16/2026
Tank Steel Single Wall Not applicable Not applicable
Vent, Riser, Fill Piping Steel risers Not applicable Not applicable

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test (Piping) Pass 5/16/2023
Tank Steel Single Wall Precision Test (Tank) Pass 5/6/2024



Tank Number 2

Capacity: 8000 Petroleum Use: None
Product: Diesel Fuel CERCLA Substance:
Status: Abandoned in place CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/6/1986 Abandoned Material: Inert material mixed with portland cement
Current Age: 44 Abandoned Date: 3/14/2019
Install Date: 1/11/1982 Red Tag Issue Date:
Last Used Date: 1/17/2019 Fee Due: $0.00
Product Date:

Equipment Information

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 10/7/2015 10/7/2018
Corrosion Prot - Piping Fiberglass Non-Corrosive Not applicable Not applicable
Corrosion Prot - Tank Lining Materials Internal Bridgeport Chemical Glass Armor GA 27P 1/22/2014 1/22/2019
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 11/30/2018 11/30/2019
Leak Detect - Tank Ground Water Monitoring Wells No passing test found No passing test found
Overfill Prev Device Overfill Drop Tube Valve 10/25/2018 10/25/2021
Piping Fiberglass Single Wall Piping Not applicable Not applicable
Spill Contain Device Single Wall Spill Bucket 9/12/2018 9/12/2021
Tank Steel Single Wall Not applicable Not applicable
Vent, Riser, Fill Piping Steel risers Not applicable Not applicable

Additional Tests

No Tests Listed




Tank Number 3

Capacity: 8000 Petroleum Use: None
Product: B-11 CERCLA Substance:
Status: Condemned Tank CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/6/1986 Abandoned Material:
Current Age: 44 Abandoned Date:
Install Date: 1/11/1982 Red Tag Issue Date: 11/14/2024
Last Used Date: 11/14/2024 Fee Due: $0.00
Product Date:

Equipment Information

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 12/15/2022 12/15/2025
Corrosion Prot - Piping Sacrificial Anode Flex Connector 12/15/2022 12/15/2025
Corrosion Prot - Piping Sacrificial Anode Flex Connector 12/15/2022 12/15/2025
Corrosion Prot - Piping Sacrificial Anode Flex Connector 12/15/2022 12/15/2025
Corrosion Prot - Piping Fiberglass Non-Corrosive Not applicable Not applicable
Corrosion Prot - Tank Lining Materials Internal Bridgeport Chemical Glass Armor GA 27P 5/2/2024 5/2/2029
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 5/16/2023 5/16/2024
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 Plus with CSLD 5/16/2023 5/16/2024
Overfill Prev Device Overfill Drop Tube Valve 5/16/2023 5/16/2026
Piping Fiberglass Single Wall Piping Not applicable Not applicable
Piping Not Installed STP/Tanktop Sump Not applicable Not applicable
Spill Contain Device Single Wall Spill Bucket 5/16/2023 5/16/2026
Tank Steel Single Wall Not applicable Not applicable
Vent, Riser, Fill Piping Steel risers Not applicable Not applicable

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test (Piping) Pass 5/16/2023
Tank Steel Single Wall Precision Test (Tank) Pass 5/6/2024



Tank Number 4

Capacity: 8000 Petroleum Use: None
Product: Gasoline - Regular CERCLA Substance:
Status: Condemned Tank CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/6/1986 Abandoned Material:
Current Age: 44 Abandoned Date:
Install Date: 1/11/1982 Red Tag Issue Date: 11/14/2024
Last Used Date: 11/14/2024 Fee Due: $0.00
Product Date:

Equipment Information

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 12/15/2022 12/15/2025
Corrosion Prot - Piping Sacrificial Anode Flex Connector 12/15/2022 12/15/2025
Corrosion Prot - Piping Sacrificial Anode Flex Connector 12/15/2022 12/15/2025
Corrosion Prot - Piping Sacrificial Anode Flex Connector 12/15/2022 12/15/2025
Corrosion Prot - Piping Fiberglass Non-Corrosive Not applicable Not applicable
Corrosion Prot - Tank Lining Materials Internal Bridgeport Chemical Glass Armor GA 27P 5/2/2024 5/2/2029
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 5/16/2023 5/16/2024
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 Plus with CSLD 5/16/2023 5/16/2024
Overfill Prev Device Overfill Drop Tube Valve 5/16/2023 5/16/2026
Piping Fiberglass Single Wall Piping Not applicable Not applicable
Piping Not Installed STP/Tanktop Sump Not applicable Not applicable
Spill Contain Device Single Wall Spill Bucket 5/16/2023 5/16/2026
Tank Steel Single Wall Not applicable Not applicable
Vent, Riser, Fill Piping Steel risers Not applicable Not applicable

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test (Piping) Pass 5/16/2023
Tank Steel Single Wall Precision Test (Tank) Pass 5/6/2024

Failed test = the latest test has failed.

Not applicable = a test does not apply to this equipment type or configuration.

No passing test found = a passing test is expected but was not found from the source data.


Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump Not applicable Not applicable



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump Not applicable Not applicable



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump Not applicable Not applicable

Failed test = the latest test has failed.

Not applicable = a test does not apply to this equipment type or configuration.

No passing test found = a passing test is expected but was not found from the source data.


MFD Motorfuel Dispensing Forms