Notice of Violations (Current)
NOV Number:
E0020252194
(Referred to Legal)
Issue Date:
8/25/2025
Expiration Date:
10/24/2025
View NOV Form
| Tanks |
Violations |
| Facility |
A/B operator retraining required as a result of issuance of the Notice of Violation and must be completed within 30 days. |
| 3 |
Line leak detection equipment in alarm or failed test, must repair or replace. - Sump sensor alarm |
| Facility |
Missing copies of 30 day Walkthrough Inspection Report. |
| 3 |
Monthly line interstitial sensor records not available. |
| 3 |
Piping interstitial must be open in all sumps - Remove spray foam from secodary piping in STP sump. |
| 3 |
Required monthly tank interstitial sensor records not available. |
| 3 |
Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. |
IEMA Numbers Associated with the Facility
No IEMA Numbers Found
LUST
Fund Eligibility and Deductibility Determinations
No Applications Found
Tank Number 1
| Capacity: |
19055 |
|
Petroleum Use: |
|
| Product: |
Diesel Fuel |
|
CERCLA Substance: |
|
| Status: |
Abandoned in place |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
1/15/1988 |
|
Abandoned Material: |
Inert material mixed with portland cement |
| Current Age: |
20 |
|
Abandoned Date: |
3/17/1997 |
| Install Date: |
|
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
|
| Product Date: |
|
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 2
| Capacity: |
4000 |
|
Petroleum Use: |
|
| Product: |
Diesel Fuel |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
2/23/2009 |
|
OSFM
First Notify Date: |
5/6/1997 |
|
Abandoned Material: |
|
| Current Age: |
11 |
|
Abandoned Date: |
|
| Install Date: |
4/25/1997 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
6/1/2001 |
|
Fee Due: |
$0.00 |
| Product Date: |
4/26/1997 |
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 3
| Capacity: |
5000 |
|
Petroleum Use: |
|
| Product: |
Gasoline - Regular |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
5/6/1997 |
|
Abandoned Material: |
|
| Current Age: |
29 |
|
Abandoned Date: |
|
| Install Date: |
4/25/1997 |
|
Red Tag Issue Date: |
10/29/2025 |
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
4/26/1997 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Electronic Pressurized Line Leak Detection |
9/17/2025 |
9/17/2026 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 350 |
9/17/2025 |
9/17/2026 |
|
Leak Detect - Tank
|
Non-Discriminating Interstitial Monitoring Sensors |
9/17/2025 |
9/17/2026 |
|
Overfill Prev Device
|
Overfill Alarm |
12/2/2024 |
12/2/2027 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
12/2/2024 |
12/2/2027 |
|
Piping
|
Fiberglass Double Wall |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
12/2/2024 |
12/2/2027 |
Leak Detect - Piping
|
Sump Sensor |
12/2/2024 |
12/2/2027 |
|
Spill Contain Device
|
Single Wall Spill Bucket |
12/2/2024 |
12/2/2027 |
|
Tank
|
Fiberglass Double Wall |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Fiberglass Double Wall
|
Precision Test (Piping)
|
Pass
|
12/6/2019
|
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
Dispenser Information
Name\ID Gas
| Status: |
Active |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Single Wall UDC Sump |
Not applicable
|
Not applicable
|
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated Not Required |
Not applicable
|
Not applicable
|
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
MFD
Motorfuel Dispensing Forms
No Forms Found