Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 7017720
Status: Active
Facility Name: ROC One Stop
Address: 1201 W. Main
West Frankfort, IL 62896
County: Franklin
Property Parcel: 11-24-304-009
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Z001147
Green Tag Issue Date: 1/26/2024
Green Tag Expiration Date: 12/31/2026

Owner Details

Owner Name: Russell Oil Company
Owner Address: 200 E. Main
Galatia, IL 62935
Owner Status: Current Owner
Purchase Date: 10/1/2011
Type of Financial Responsibility: Certificate of Deposit
Financial Responsibility Reporting Due Date: 1/14/2026

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 1/26/2024 12/31/2026

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0013266 Russell Oil Company Current Owner 10/1/2011
U0032266 4-Villy Former Owner 4/21/2004
U0034897 West Frankfort, Inc. Former Owner
U0016432 Willi Oil Co. Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violations (Current)

No Notice of Violations Found

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
05-1512 11/8/2005 Removal Log 01123-2005REM
14-0670 7/2/2014 Removal Log 00586-2014REM
90-2823 9/26/1990 Removal Log
N/A 11/6/2017 Removal Log 01231-2017REM

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
14-0670 Eligible 7/31/2014 9/11/2014 $5,000
Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 6000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 9/26/1990
OSFM First Notify Date: 3/31/1986 Abandoned Material:
Current Age: 19 Abandoned Date:
Install Date: 1/1/1971 Red Tag Issue Date:
Last Used Date: 9/24/1990 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 2

Capacity: 4000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 9/26/1990
OSFM First Notify Date: 3/31/1986 Abandoned Material:
Current Age: 19 Abandoned Date:
Install Date: 1/1/1971 Red Tag Issue Date:
Last Used Date: 9/24/1990 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 3

Capacity: 4000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 9/26/1990
OSFM First Notify Date: 3/31/1986 Abandoned Material:
Current Age: 19 Abandoned Date:
Install Date: 1/1/1971 Red Tag Issue Date:
Last Used Date: 9/24/1990 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 4

Capacity: 4000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 9/26/1990
OSFM First Notify Date: 3/31/1986 Abandoned Material:
Current Age: 19 Abandoned Date:
Install Date: 1/1/1971 Red Tag Issue Date:
Last Used Date: 9/24/1990 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 5

Capacity: 560 Petroleum Use:
Product: Used Oil CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 11/8/2005
OSFM First Notify Date: 9/28/1990 Abandoned Material:
Current Age: 34 Abandoned Date:
Install Date: 1/1/1971 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 6

Capacity: 560 Petroleum Use:
Product: Heating Oil CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 11/8/2005
OSFM First Notify Date: 9/28/1990 Abandoned Material:
Current Age: 34 Abandoned Date:
Install Date: 1/1/1971 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 7

Capacity: 8000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 7/2/2014
OSFM First Notify Date: 6/7/1991 Abandoned Material:
Current Age: 23 Abandoned Date:
Install Date: 10/12/1990 Red Tag Issue Date:
Last Used Date: 6/11/2014 Fee Due: $0.00
Product Date: 10/18/1990

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank STIP3 Cathodic Protection with Dielectric Coating 4/16/2013 4/16/2016
Leak Detect - Piping Electronic Pressurized Line Leak Detection 4/15/2014 4/15/2015
Leak Detect - Piping Sump Sensor 4/15/2014 4/15/2015
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD
Overfill Prev Device Overfill Drop Tube Valve
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Spill Contain Device Single Wall Spill Bucket
Tank Steel Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 8

Capacity: 8000 Petroleum Use:
Product: E85 CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 7/2/2014
OSFM First Notify Date: 6/7/1991 Abandoned Material:
Current Age: 23 Abandoned Date:
Install Date: 10/12/1990 Red Tag Issue Date:
Last Used Date: 6/11/2014 Fee Due: $0.00
Product Date: 10/18/1990

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank STIP3 Cathodic Protection with Dielectric Coating 4/16/2013 4/16/2016
Leak Detect - Piping Electronic Pressurized Line Leak Detection 4/15/2014 4/15/2015
Leak Detect - Piping Sump Sensor 4/15/2014 4/15/2015
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD
Overfill Prev Device Overfill Drop Tube Valve
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Spill Contain Device Single Wall Spill Bucket
Tank Steel Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 9

Capacity: 8000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 7/2/2014
OSFM First Notify Date: 6/7/1991 Abandoned Material:
Current Age: 23 Abandoned Date:
Install Date: 10/12/1990 Red Tag Issue Date:
Last Used Date: 6/11/2014 Fee Due: $0.00
Product Date: 10/18/1990

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank STIP3 Cathodic Protection with Dielectric Coating 4/16/2013 4/16/2016
Leak Detect - Piping Electronic Pressurized Line Leak Detection 4/15/2014 4/15/2015
Leak Detect - Piping Sump Sensor 4/15/2014 4/15/2015
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD
Overfill Prev Device Overfill Drop Tube Valve
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Spill Contain Device Single Wall Spill Bucket
Tank Steel Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 10

Capacity: 16000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 8/21/2014 Abandoned Material:
Current Age: 10 Abandoned Date:
Install Date: 7/16/2014 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 7/17/2014

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Composite Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 5/2/2025 5/2/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 5/2/2025 5/2/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 5/2/2025 5/2/2026
Overfill Prev Device Overfill Drop Tube Valve 5/1/2024 5/1/2027
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping STP/Tanktop Sump containment FRP 5/1/2024 5/1/2027
Leak Detect - Piping Sump Sensor with positive shutdown 5/2/2025 5/2/2026
Spill Contain Device Single Wall Spill Bucket 5/1/2024 5/1/2027
Tank Composite Double Wall Modern Welding Glasteel II N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 5/2/2025



Tank Number 11

Capacity: 8000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 11/6/2017
OSFM First Notify Date: 8/21/2014 Abandoned Material:
Current Age: 3 Abandoned Date:
Install Date: 7/16/2014 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 7/17/2014

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Composite Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 4/21/2017 4/21/2018
Leak Detect - Piping Sump Sensor 4/21/2017 4/21/2018
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 4/21/2017 4/21/2018
Overfill Prev Device Overfill Drop Tube Valve
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping STP/Tanktop Sump containment FRP
Spill Contain Device Single Wall Spill Bucket
Tank Composite Double Wall Modern Welding Glasteel II N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 12

Capacity: 8000 Petroleum Use:
Product: E85 CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 11/6/2017
OSFM First Notify Date: 8/21/2014 Abandoned Material:
Current Age: 3 Abandoned Date:
Install Date: 7/16/2014 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 7/17/2014

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Composite Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 4/21/2017 4/21/2018
Leak Detect - Piping Sump Sensor 4/21/2017 4/21/2018
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 4/21/2017 4/21/2018
Overfill Prev Device Overfill Drop Tube Valve
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping STP/Tanktop Sump containment FRP
Spill Contain Device Single Wall Spill Bucket
Tank Composite Double Wall Modern Welding Glasteel II N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 13

Capacity: 8000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 11/21/2017 Abandoned Material:
Current Age: 7 Abandoned Date:
Install Date: 11/9/2017 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 11/9/2017

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Composite Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 5/2/2025 5/2/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 5/2/2025 5/2/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 5/2/2025 5/2/2026
Overfill Prev Device Overfill Drop Tube Valve 5/1/2024 5/1/2027
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Fiberglass Double Wall Ameron N/A N/A
Piping Single Wall STP/Tanktop Sump 5/1/2024 5/1/2027
Leak Detect - Piping Sump Sensor with positive shutdown 5/2/2025 5/2/2026
Spill Contain Device Single Wall Spill Bucket 5/1/2024 5/1/2027
Tank Composite Double Wall Modern Welding Glasteel II N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Precision Test (Piping) Pass 5/2/2025
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 5/2/2025



Tank Number 14

Capacity: 8000 Petroleum Use:
Product: E15 CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 11/21/2017 Abandoned Material:
Current Age: 7 Abandoned Date:
Install Date: 11/9/2017 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 11/9/2017

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Composite Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 5/2/2025 5/2/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 5/2/2025 5/2/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 5/2/2025 5/2/2026
Overfill Prev Device Overfill Drop Tube Valve 5/1/2024 5/1/2027
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Fiberglass Double Wall Ameron N/A N/A
Piping Single Wall STP/Tanktop Sump 5/1/2024 5/1/2027
Leak Detect - Piping Sump Sensor with positive shutdown 5/2/2025 5/2/2026
Spill Contain Device Single Wall Spill Bucket 5/1/2024 5/1/2027
Tank Composite Double Wall Modern Welding Glasteel II N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Precision Test (Piping) Pass 5/2/2025
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 5/2/2025

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 5/1/2024 5/1/2027
Leak Detect - Piping Sump Sensor with positive shutdown 5/2/2025 5/2/2026



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 5/1/2024 5/1/2027
Leak Detect - Piping Sump Sensor with positive shutdown 5/2/2025 5/2/2026



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 5/1/2024 5/1/2027
Leak Detect - Piping Sump Sensor with positive shutdown 5/2/2025 5/2/2026



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 5/1/2024 5/1/2027
Leak Detect - Piping Sump Sensor with positive shutdown 5/2/2025 5/2/2026



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 5/1/2024 5/1/2027
Leak Detect - Piping Sump Sensor with positive shutdown 5/2/2025 5/2/2026

MFD Motorfuel Dispensing Forms

No Forms Found