1, 3, 4 |
Failed to Empty the Tank to 1" or Less - Per 175.810(a)(1), when placing tanks out of service, the tank and lines must be emptied immediately. The UST is considered empty when all materials have been removed to one inch or less. Upon my inspection on 1/4/24, I took stick readings of each tank and tanks #1, 3 & 4 still had more than an inch of product. Tanks were red tagged on 2/28/19. |
Facility |
Financial responsibility must be reported yearly - Financial Responsibility must be declared annually. The form can be found at: https://webapps.sfm.illinois.gov/USTPortal/Forms/FinancialResponsibility. |
1, 2, 3, 4 |
Remove tank(s) - Single-Walled, Over 30 Years Old and OOS Over One Year - Single walled tanks were taken out of service on 02/28/19, and are 43 years old. Per 175.810(e) tanks must be removed as they are now condemned. Here is a link to the licensed UST Decommissioning contractors, that can perform UST tank removals:
https://webapps.sfm.illinois.gov/ustsearch/ContractorSearch.aspx |