| 19, 20, 21, 22, 23, 24 |
Line interstitial sensors have been raised and rendered inoperational. - Dispenser sumps #1/2, 5/6, 11/12, 13/14, 15/16, 17 Master, 21 Master, 22, Master, Diesel STP(T3) |
| Facility |
Miscellaneous - Each emergency stop shall be identified by a sign on all-weather materials stating "EMERGENCY STOP" in 2 inch red capital letters. 7 emergency stop buttons located by the dispenser islands are not identified. |
| 23, 24 |
Miscellaneous - Spill prevention equipment device requires repair. |
| 21 |
Monthly line interstitial sensor records not available. - Diesel 1 STP sump sensor removed from ATG programming. Repair/replace sensor. |
| 19, 20, 21, 22, 23, 24 |
Piping interstitial must be open in all sumps |
| 21, 22, 23, 24 |
Shear valve(s) not in proper working order. - Upon inspection the shear valve is tripped but did not close. Repair/replace. |