Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 7013258
Status: Active
Facility Name: ROC One Stop #11
Address: 531 East Vine Street Vienna, IL 62995
County: Johnson
Property Parcel: 0000000000
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y000608
Green Tag Issue Date: 1/12/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: Russell Oil Company
Owner Address: 200 E. Main Galatia, IL 62935
Owner Status: Current Owner
Purchase Date: 8/11/2010
Type of Financial Responsibility: Certificate of Deposit
Financial Responsibility Reporting Due Date: 1/14/2026

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 1/12/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0013266 Russell Oil Company Current Owner 8/11/2010
U0034027 W-4 Holdings, Inc. Former Owner 2/1/2007
U0033329 JAJB Investments, Inc. Former Owner 1/24/2006
U0032805 Shane Investments, Inc. Former Owner 5/20/2005
U0030760 Golightly & Long, LLC Former Owner 5/1/2002
U0022089 Duke & Long Distributing Co., Inc. Former Owner 12/1/1994
U0014099 Smoot Oil Company, Inc. Former Owner 12/31/1967

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020252183 (Pending)    Issue Date: 8/22/2025    Expiration Date: 10/21/2025    View NOV Form

Tanks Violations
4, 5, 6, 7 Line interstitial sensors have been raised and rendered inoperational. - Dispenser sump sensors raised #1/2, 3/4, 7/8, 9/10. Sensors must be located on the bottom at the lowest point of containment.
4, 6 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.

NOV Number: E0020252184 (Pending)    Issue Date: 8/22/2025    Expiration Date: 10/21/2025    View NOV Form

Tanks Violations
Facility Code complying instruction/warning signs are not properly mounted at each dispenser island - Minimum Signage. Signs shall be provided that are clearly visible to all self-service customers. The signs shall be made of all-weather material and the lettering shall be not less than ? inch high. The top of the signs shall be mounted no higher than 10 feet above grade, or at a height approved by OSFM, and shall include the following wording, at a minimum: 1) "Warning"; 2) "Stop Engine"; 3) "No Smoking"; 4) "Persons fueling vehicles shall remain with their vehicle, at the nozzle, while fueling is in progress"; 5) "It is unlawful and dangerous for anyone to dispense gasoline into unapproved containers".

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
10-0769 8/4/2010 Removal Log 00866-2010REM

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
10-0769 Eligible 9/7/2010 11/1/2010 $5,000
Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 12000 Gasoline Removed Federal $0.00 08/04/2010 - REM
2 12000 Gasoline Removed Federal $0.00 08/04/2010 - REM
3 6000 Gasoline Removed Federal $0.00 08/04/2010 - REM
4 15000 Gasoline - Regular Currently in use Federal $0.00
5 5000 Gasoline - Premium Currently in use Federal $0.00
6 5000 E15 Currently in use Federal $0.00
7 5000 Diesel Fuel Currently in use Federal $0.00

Dispenser Information

Name\ID Status
1/2 Active
3/4 Active
5/6 Active
7/8 Active
9/10 Active

MFD Motorfuel Dispensing Forms