8 |
Line leak detection equipment in alarm or failed test, must repair or replace. - Diesel STP West Sensor in alarm, water in sump. |
Facility |
Missing copies of current testing certificates for operator training - No Class C Operators at an attended facility. |
Facility |
Missing list of designated Class A/B & C Operators |
8 |
Piping interstitial must be open in all sumps |
5, 6, 7 |
Shear valve(s) not properly mounted and/or not at proper height. - Shear valves too low and not properly mounted, missing mounting bolts. |
8 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. |
8 |
Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. - Diesel STP sumps. |
5, 7 |
Water in containment without required interstitial sensors - install cathodic protection on all exposed steel. |