Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 7011747
Status: Active
Facility Name: Mitchellville Country Store
Address: 5850 Highway 145 South Harrisburg, IL 62946
County: Saline
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y000953
Green Tag Issue Date: 8/3/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: 2 James, LLC
Owner Address: 5850 Hwy 145 Harrisburg, IL 62946
Owner Status: Current Owner
Purchase Date: 8/1/2012
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 7/16/2026

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 8/3/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0036657 2 James, LLC Current Owner 8/1/2012
U0032920 People's National Bank Former Owner 11/1/2008
U0028595 Hathaway, Jeff Former Owner 3/3/1999
U0035188 Kuhl-Fox, LLC Former Owner

Permits (Unexpired)

Click for permit history
Permit Number Type Status OSFM Receive Date Issue Date Expiration Date Documents
00300-2025UPG Upgrade Approved / Issued 3/6/2025 3/13/2025 9/15/2025 Documents
01084-2025UPG Upgrade Approved / Issued 8/19/2025 8/19/2025 2/19/2026 Documents

Notice of Violatlions (Current)

NOV Number: E0020251992 (Pending)    Issue Date: 8/7/2025    Expiration Date: 10/6/2025    View NOV Form

Tanks Violations
8 Line leak detection equipment in alarm or failed test, must repair or replace. - Diesel STP West Sensor in alarm, water in sump.
Facility Missing copies of current testing certificates for operator training - No Class C Operators at an attended facility.
Facility Missing list of designated Class A/B & C Operators
8 Piping interstitial must be open in all sumps
5, 6, 7 Shear valve(s) not properly mounted and/or not at proper height. - Shear valves too low and not properly mounted, missing mounting bolts.
8 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.
8 Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. - Diesel STP sumps.
5, 7 Water in containment without required interstitial sensors - install cathodic protection on all exposed steel.

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
991645 7/9/1999 Removal Log 01944-1999REM

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
99-0694 Eligible 8/12/1999 8/25/1999 $15,000
Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 3000 Gasoline Removed Federal $0.00 07/09/1999 - REM
2 1120 Gasoline Removed Federal $0.00 07/09/1999 - REM
3 2000 Gasoline Removed Federal $0.00 07/09/1999 - REM
4 1000 Heating Oil Removed State $0.00 07/09/1999 - REM
5 12000 Gasoline - Regular Currently in use Federal $0.00
6 8000 Diesel Fuel Currently in use Federal $0.00
7 4000 Gasoline - Premium Currently in use Federal $0.00
8 30000 Diesel Fuel Currently in use Federal $0.00

Dispenser Information

Name\ID Status
10 Satellite Active
7 Active
10 Active
8 Active
9 Active
1/2 Active
3/4 Active
5/6 Active
6S Active

MFD Motorfuel Dispensing Forms

No Forms Found