Notice of Violatlions (Current)
NOV Number:
E0020252924
(Pending)
Issue Date:
11/3/2025
Expiration Date:
1/2/2026
View NOV Form
| Tanks |
Violations |
| 10 |
Line interstitial sensors have been raised and rendered inoperational. - Raised sensor in East STP sump. |
| 10, 11, 12, 13 |
Piping interstitial must be open in all sumps - STP sumps Premium, Non Ethanol, and B-11 need interstitial opened. Dispenser 1/2 sump needs interstitial opened. |
| 10 |
Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. - Water in East STP sump. |