Owner Summary
Click for Facility/Tank Ownership history
| Owner Number |
Owner Name |
Owner Status |
Purchase Date |
| U0030949 |
Mac's Convenience Stores, LLC |
Current Owner |
8/27/2003 |
| U0029789 |
Clark Retail Enterprises, Inc. |
Former Owner |
3/7/2001 |
| U0015989 |
Wareco Service, Inc. |
Former Owner |
1/1/1977 |
Notice of Violations (Current)
NOV Number:
E0020261573
(Pending)
Issue Date:
6/17/2026
Expiration Date:
8/16/2026
View NOV Form
| Tanks |
Violations |
| 1 |
Dispensers - the following hoses or breakaways are missing or actively leaking and require immediate replacement (bagged at inspection) |
| 6 |
Line interstitial sensors have been raised and rendered inoperational. - Premium STP sump sensor cannot be on top of the manway. Remove liquid from the bottom of the sump and lower the sensor to the lowest point of containment. |
| 1, 5, 6 |
Piping interstitial must be open in all sumps |
| 1, 5, 6 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. |
IEMA Numbers Associated with the Facility
| IEMA Number |
Inspection Date |
Inspection Type |
Permit Number |
| 18-0183 |
2/21/2018 |
Removal Log |
01595-2017REM |
LUST
Fund Eligibility and Deductibility Determinations
| IEMA Number |
Status |
OSFM Received Date |
OSFM Response Date |
Deductible |
Letter |
| 97-2255 |
Eligible |
8/30/1999
|
9/10/1999
|
$10,000
|
|
| 98-0771 |
Eligible |
9/20/1999
|
9/29/1999
|
$10,000
|
|
| 97-2255 |
Eligible |
5/22/2006
|
6/23/2006
|
$10,000
|
|
| 98-0771 |
Eligible |
7/12/2006
|
8/14/2006
|
$10,000
|
|
Tank Number 1
| Capacity: |
10000 |
|
Petroleum Use: |
|
| Product: |
Diesel Fuel |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
12/27/1985 |
|
Abandoned Material: |
|
| Current Age: |
42 |
|
Abandoned Date: |
|
| Install Date: |
1/1/1984 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
|
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Flexible Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Electronic Pressurized Line Leak Detection |
3/24/2026 |
3/24/2027 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 350 with CSLD |
4/6/2026 |
4/6/2027 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
4/30/2024 |
4/30/2027 |
|
Piping
|
Flexible Double Wall |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
4/9/2025 |
4/9/2028 |
Leak Detect - Piping
|
Sump Sensor |
4/9/2025 |
4/9/2028 |
|
Spill Contain Device
|
Double Wall Spill Bucket |
4/30/2024 |
4/30/2027 |
|
Tank
|
Fiberglass Single Wall |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Flexible Double Wall
|
Precision Test (Piping)
|
Pass
|
3/24/2026
|
Tank Number 2
| Capacity: |
10000 |
|
Petroleum Use: |
|
| Product: |
Gasoline |
|
CERCLA Substance: |
|
| Status: |
Abandoned in place |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
12/27/1985 |
|
Abandoned Material: |
Inert material mixed with portland cement |
| Current Age: |
53 |
|
Abandoned Date: |
4/7/1998 |
| Install Date: |
1/1/1973 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
4/6/1998 |
|
Fee Due: |
$0.00 |
| Product Date: |
|
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 3
| Capacity: |
10000 |
|
Petroleum Use: |
|
| Product: |
Gasoline |
|
CERCLA Substance: |
|
| Status: |
Abandoned in place |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
12/27/1985 |
|
Abandoned Material: |
Inert material mixed with portland cement |
| Current Age: |
53 |
|
Abandoned Date: |
4/7/1998 |
| Install Date: |
1/1/1973 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
4/6/1998 |
|
Fee Due: |
$0.00 |
| Product Date: |
|
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 4
| Capacity: |
2000 |
|
Petroleum Use: |
|
| Product: |
Kerosene |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
2/21/2018 |
|
OSFM
First Notify Date: |
12/27/1985 |
|
Abandoned Material: |
|
| Current Age: |
34 |
|
Abandoned Date: |
|
| Install Date: |
1/1/1984 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
11/28/2017 |
|
Fee Due: |
$0.00 |
| Product Date: |
|
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Flexible Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Lining Materials Internal |
9/5/2012 |
9/5/2017 |
|
Leak Detect - Piping
|
Electronic Pressurized Line Leak Detection |
8/30/2017 |
8/30/2018 |
|
Leak Detect - Piping
|
Sump Sensor |
8/30/2017 |
8/30/2018 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 350 with CSLD |
No passing test found |
No passing test found |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
No passing test found |
No passing test found |
|
Piping
|
Flexible Double Wall |
Not applicable |
Not applicable |
|
Spill Contain Device
|
Single Wall Spill Bucket |
No passing test found |
No passing test found |
|
Tank
|
Steel Single Wall |
Not applicable |
Not applicable |
Additional Tests
No Tests Listed
Tank Number 5
| Capacity: |
12000 |
|
Petroleum Use: |
|
| Product: |
Gasoline - Regular |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
6/10/1998 |
|
Abandoned Material: |
|
| Current Age: |
28 |
|
Abandoned Date: |
|
| Install Date: |
4/10/1998 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
4/10/1998 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Flexible Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Electronic Pressurized Line Leak Detection |
3/24/2026 |
3/24/2027 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 350 with CSLD |
4/6/2026 |
4/6/2027 |
|
Leak Detect - Tank
|
Non-Discriminating Interstitial Monitoring Sensors |
3/24/2026 |
3/24/2027 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
4/30/2024 |
4/30/2027 |
|
Piping
|
Flexible Double Wall |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
4/9/2025 |
4/9/2028 |
Leak Detect - Piping
|
Sump Sensor |
4/9/2025 |
4/9/2028 |
|
Spill Contain Device
|
Double Wall Spill Bucket |
4/30/2024 |
4/30/2027 |
|
Tank
|
Fiberglass Double Wall |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Flexible Double Wall
|
Precision Test (Piping)
|
Pass
|
3/24/2026
|
Tank Number 6
| Capacity: |
12000 |
|
Petroleum Use: |
|
| Product: |
Gasoline - Premium |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
6/10/1998 |
|
Abandoned Material: |
|
| Current Age: |
28 |
|
Abandoned Date: |
|
| Install Date: |
4/10/1998 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
4/10/1998 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Flexible Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Electronic Pressurized Line Leak Detection |
3/24/2026 |
3/24/2027 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 350 with CSLD |
4/6/2026 |
4/6/2027 |
|
Leak Detect - Tank
|
Non-Discriminating Interstitial Monitoring Sensors |
3/24/2026 |
3/24/2027 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
4/30/2024 |
4/30/2027 |
|
Piping
|
Flexible Double Wall |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
4/9/2025 |
4/9/2028 |
Leak Detect - Piping
|
Sump Sensor with positive shutdown |
4/9/2025 |
4/9/2028 |
|
Spill Contain Device
|
Double Wall Spill Bucket |
4/30/2024 |
4/30/2027 |
|
Tank
|
Fiberglass Double Wall |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Flexible Double Wall
|
Precision Test (Piping)
|
Pass
|
3/24/2026
|
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
MFD
Motorfuel Dispensing Forms
| Facility Number |
Name |
City |
Received Date |
Letter |
|
7006086
|
Circle K #1231
|
Murphysboro
|
11/15/2024
|
Letter
Form
|