Notice of Violations (Current)
NOV Number:
E0020261573
(Pending)
Issue Date:
6/17/2026
Expiration Date:
8/16/2026
View NOV Form
| Tanks |
Violations |
| 1 |
Dispensers - the following hoses or breakaways are missing or actively leaking and require immediate replacement (bagged at inspection) |
| 6 |
Line interstitial sensors have been raised and rendered inoperational. - Premium STP sump sensor cannot be on top of the manway. Remove liquid from the bottom of the sump and lower the sensor to the lowest point of containment. |
| 1, 5, 6 |
Piping interstitial must be open in all sumps |
| 1, 5, 6 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. |