Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 7005864
Status: Active
Facility Name: Creal Springs Mini Mart, Inc.
Address: 100 E. Keely, Route 166
Creal Springs, IL 62922
County: Williamson
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y000967
Green Tag Issue Date: 10/24/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: Creal Springs Mini Mart, Inc.
Owner Address:
Owner Status: Current Owner
Purchase Date: 5/20/2005
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 8/24/2025

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 10/24/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0032790 Creal Springs Mini Mart, Inc. Current Owner 5/20/2005
U0006932 Holliday Oil Company, Inc. Former Owner 11/23/1989

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violations (Current)

NOV Number: E0020251069 (Pending)    Issue Date: 4/18/2025    Expiration Date: 6/17/2025    View NOV Form

Tanks Violation
Facility Annual Emergency Stop Inspection not completed or inspection report not available.
Facility Control station not equipped with an emergency shutoff switch - Presently located out of the control station.
5, 7 Dispensers - hoses cracked, split or worn and require replacement - Whip hose needs replaced.
Facility Missing copies of 30 day Walkthrough Inspection Report. - Missing 30 day walkthrough for 2025
Facility Missing copies of Annual Walkthrough Inspection Report.
Facility Missing list of designated Class A/B & C Operators
4, 5, 7 Not Vented Properly - Collision prevention is required for the vents.
4 Open electrical conduit or junction boxes. - Probe wire connection does not comply
4, 5, 7 Required monthly tank leak test records not available. - No passing leak tests available for inspection
4 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.
4, 5, 7 Tank precision test required. - Due to violations test required

NOV Number: E0020251070 (Pending)    Issue Date: 4/18/2025    Expiration Date: 6/17/2025    View NOV Form

Tanks Violation
Facility Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable
Facility Fire Extinguishers - Past due for annual testing
Facility Miscellaneous - Each emergency stop shall be identified by a sign on all-weather materials stating "EMERGENCY STOP" in 2 inch red capital letters.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 1000 Gasoline Removed Federal $0.00 10/11/1989 - REM
2 2000 Gasoline Removed Federal $0.00 10/11/1989 - REM
3 1000 Gasoline Removed Federal $0.00 10/11/1989 - REM
4 1000 Diesel Fuel Currently in use Federal $0.00
5 1000 Gasoline - Premium Currently in use Federal $0.00
6 2000 Gasoline Removed Federal $0.00 10/02/2000 - REM
7 4000 Gasoline - Regular Currently in use Federal $0.00

Dispenser Information

Name\ID Status
1/2 Active

MFD Motorfuel Dispensing Forms

No Forms Found