Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 7002136
Status: Active
Facility Name: Chuck Wagon Charlie's Inc.
Address: 746 County Road 2550 North Burnt Prairie, IL 62820
County: White
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y004253
Green Tag Issue Date: 12/4/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: Chuck Wagon Charlie's, Inc.
Owner Address: 2210 County Road 150N Barnhill, IL 62809
Owner Status: Current Owner
Purchase Date: 7/1/1991
Type of Financial Responsibility: Designated Savings Account
Financial Responsibility Reporting Due Date: 8/15/2024

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 12/4/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0038714 Chuck Wagon Charlie's, Inc. Current Owner 7/1/1991
U0020805 Whetstone Food Mart, Former Owner 7/1/1991
U0016321 Whetstone Steven L Former Owner 12/31/1967

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020252063 (Pending)    Issue Date: 8/13/2025    Expiration Date: 10/12/2025    View NOV Form

Tanks Violations
Facility A/B operator retraining required as a result of issuance of the Notice of Violation
Facility Financial responsibility must be reported yearly - Financial Responsibility must be declared annually. The form can be found at https://webapps.sfm.illinois.gov/USTPortal/Forms/FinancialResponsibility.
5 Flex connector sacrificial anode system not tested (required every 3 years) - Test anodes and replace as needed - Diesel dispenser anode requires testing.
Facility Missing copies of 30 day Walkthrough Inspection Report. - Two years of 30 day inspections required to be maintained for inspection.
Facility Missing copies of current testing certificates for operator training - Missing valid Class A/B and Class C certificates.
Facility Missing list of designated Class A/B & C Operators
4, 5, 6 Required monthly tank leak test records not available. - Two years of monthly leak records not available.
4, 5, 6 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.
4, 5 Water in containment without required interstitial sensors - install cathodic protection on all exposed steel. - Regular unleaded and Diesel STP sumps require cathodic protection due to water ingress.

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
06-0518 5/2/2006 Removal Log 00396-2006REM

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
06-0084 Eligible 4/14/2006 4/25/2006 $10,000
Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 10000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 5/2/2006
OSFM First Notify Date: 3/17/1986 Abandoned Material:
Current Age: 22 Abandoned Date:
Install Date: 11/1/1983 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 11/1/1983

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 2

Capacity: 10000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 5/2/2006
OSFM First Notify Date: 3/17/1986 Abandoned Material:
Current Age: 22 Abandoned Date:
Install Date: 11/1/1983 Red Tag Issue Date:
Last Used Date: 1/1/2006 Fee Due: $0.00
Product Date: 11/1/1983

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 3

Capacity: 10000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 5/2/2006
OSFM First Notify Date: 3/17/1986 Abandoned Material:
Current Age: 22 Abandoned Date:
Install Date: 11/1/1983 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 11/1/1983

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 4

Capacity: 10000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/23/2006 Abandoned Material:
Current Age: 19 Abandoned Date:
Install Date: 5/8/2006 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 5/19/2006

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Composite Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 5/1/2025 5/1/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 300 5/1/2025 5/1/2026
Overfill Prev Device Overfill Drop Tube Valve 8/17/2023 8/17/2026
Piping Flexible Double Wall Total Containment Enviroflex non-corrosive N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Double Wall Spill Bucket 8/25/2023 8/25/2026
Tank Composite Single Wall ACT 100 N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Total Containment Enviroflex non-corrosive Precision Test (Piping) Pass 5/1/2025



Tank Number 5

Capacity: 6000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/23/2006 Abandoned Material:
Current Age: 19 Abandoned Date:
Install Date: 5/8/2006 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 5/19/2006

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Composite Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 5/1/2025 5/1/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 300 5/1/2025 5/1/2026
Overfill Prev Device Overfill Drop Tube Valve 8/17/2023 8/17/2026
Piping Flexible Double Wall Total Containment Enviroflex non-corrosive N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Single Wall Spill Bucket 8/25/2023 8/25/2026
Tank Composite Single Wall ACT 100 N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Total Containment Enviroflex non-corrosive Precision Test (Piping) Pass 5/1/2025



Tank Number 6

Capacity: 4000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/23/2006 Abandoned Material:
Current Age: 19 Abandoned Date:
Install Date: 5/8/2006 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 5/19/2006

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Composite Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 5/1/2025 5/1/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 300 5/1/2025 5/1/2026
Overfill Prev Device Overfill Drop Tube Valve 8/17/2023 8/17/2026
Piping Flexible Double Wall Total Containment Enviroflex non-corrosive N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Single Wall Spill Bucket 8/17/2023 8/17/2026
Tank Composite Single Wall ACT 100 N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Total Containment Enviroflex non-corrosive Precision Test (Piping) Pass 5/1/2025

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A

MFD Motorfuel Dispensing Forms