Notice of Violations (Current)
NOV Number:
E0020261730
(Pending)
Issue Date:
7/7/2026
Expiration Date:
9/5/2026
View NOV Form
| Tanks |
Violations |
| 1, 2, 3, 4 |
Dispensers - hoses cracked, split or worn and require replacement - Dispenser's #1,2,4,5,7,8,9,10 whip hose Reg./Prem. needs replaced. Dispenser #10 Diesel hose/ swivel needs replaced. |
IEMA Numbers Associated with the Facility
No IEMA Numbers Found
LUST
Fund Eligibility and Deductibility Determinations
No Applications Found
Tank Number 1
| Capacity: |
22000 |
|
Petroleum Use: |
|
| Product: |
Gasoline - Regular |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
8/15/2018 |
|
Abandoned Material: |
|
| Current Age: |
8 |
|
Abandoned Date: |
|
| Install Date: |
4/11/2018 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
7/19/2018 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Flexible Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Electronic Pressurized Line Leak Detection |
6/3/2026 |
6/3/2027 |
|
Leak Detect - Tank
|
Non-Discriminating Interstitial Monitoring Sensors With Monitor |
6/3/2026 |
6/3/2027 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
7/17/2024 |
7/17/2027 |
|
Piping
|
Flexible Double Wall A.P.T. Poly Tech S175SC |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
7/17/2024 |
7/17/2027 |
Leak Detect - Piping
|
Sump Sensor with positive shutdown |
7/17/2024 |
7/17/2027 |
|
Spill Contain Device
|
Single Wall Spill Bucket |
7/17/2024 |
7/17/2027 |
|
Tank
|
Fiberglass Double Wall XERXES |
Not applicable |
Not applicable |
|
Vent, Riser, Fill Piping
|
Steel risers |
Not applicable |
Not applicable |
Additional Tests
No Tests Listed
Tank Number 2
| Capacity: |
14000 |
|
Petroleum Use: |
None |
| Product: |
B-11 |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
8/15/2018 |
|
Abandoned Material: |
|
| Current Age: |
8 |
|
Abandoned Date: |
|
| Install Date: |
4/11/2018 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
7/19/2018 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Flexible Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Electronic Pressurized Line Leak Detection |
6/3/2026 |
6/3/2027 |
|
Leak Detect - Tank
|
Non-Discriminating Interstitial Monitoring Sensors With Monitor |
6/3/2026 |
6/3/2027 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
7/17/2024 |
7/17/2027 |
|
Piping
|
Flexible Double Wall A.P.T. Poly Tech S175SC |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
7/17/2024 |
7/17/2027 |
Leak Detect - Piping
|
Sump Sensor with positive shutdown |
7/17/2024 |
7/17/2027 |
|
Spill Contain Device
|
Single Wall Spill Bucket |
7/17/2024 |
7/17/2027 |
|
Tank
|
Fiberglass Double Wall XERXES |
Not applicable |
Not applicable |
|
Vent, Riser, Fill Piping
|
Steel risers |
Not applicable |
Not applicable |
Additional Tests
No Tests Listed
Tank Number 3
| Capacity: |
8000 |
|
Petroleum Use: |
|
| Product: |
Gasoline - Premium |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
8/15/2018 |
|
Abandoned Material: |
|
| Current Age: |
8 |
|
Abandoned Date: |
|
| Install Date: |
4/11/2018 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
7/19/2018 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Flexible Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Electronic Pressurized Line Leak Detection |
6/3/2026 |
6/3/2027 |
|
Leak Detect - Tank
|
Non-Discriminating Interstitial Monitoring Sensors With Monitor |
6/3/2026 |
6/3/2027 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
7/17/2024 |
7/17/2027 |
|
Piping
|
Flexible Double Wall A.P.T. Poly Tech S175SC |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
7/17/2024 |
7/17/2027 |
Leak Detect - Piping
|
Sump Sensor with positive shutdown |
7/17/2024 |
7/17/2027 |
|
Spill Contain Device
|
Single Wall Spill Bucket |
7/17/2024 |
7/17/2027 |
|
Tank
|
Fiberglass Double Wall XERXES |
Not applicable |
Not applicable |
|
Vent, Riser, Fill Piping
|
Steel risers |
Not applicable |
Not applicable |
Additional Tests
No Tests Listed
Tank Number 4
| Capacity: |
8000 |
|
Petroleum Use: |
|
| Product: |
Gasoline - Premium |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
8/15/2018 |
|
Abandoned Material: |
|
| Current Age: |
8 |
|
Abandoned Date: |
|
| Install Date: |
4/11/2018 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
7/19/2018 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Flexible Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Electronic Pressurized Line Leak Detection |
6/3/2026 |
6/3/2027 |
|
Leak Detect - Tank
|
Non-Discriminating Interstitial Monitoring Sensors With Monitor |
6/3/2026 |
6/3/2027 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
7/17/2024 |
7/17/2027 |
|
Piping
|
Flexible Double Wall A.P.T. Poly Tech S175SC |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
7/17/2024 |
7/17/2027 |
Leak Detect - Piping
|
Sump Sensor with positive shutdown |
7/17/2024 |
7/17/2027 |
|
Spill Contain Device
|
Single Wall Spill Bucket |
7/17/2024 |
7/17/2027 |
|
Tank
|
Fiberglass Double Wall XERXES |
Not applicable |
Not applicable |
|
Vent, Riser, Fill Piping
|
Steel risers |
Not applicable |
Not applicable |
Additional Tests
No Tests Listed
Tank Number 5
| Capacity: |
8000 |
|
Petroleum Use: |
|
| Product: |
E85 |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
8/15/2018 |
|
Abandoned Material: |
|
| Current Age: |
8 |
|
Abandoned Date: |
|
| Install Date: |
4/11/2018 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
7/19/2018 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Flexible Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Electronic Pressurized Line Leak Detection |
6/3/2026 |
6/3/2027 |
|
Leak Detect - Tank
|
Non-Discriminating Interstitial Monitoring Sensors With Monitor |
6/3/2026 |
6/3/2027 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
7/17/2024 |
7/17/2027 |
|
Piping
|
Flexible Double Wall A.P.T. Poly Tech S175SC |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
7/17/2024 |
7/17/2027 |
Leak Detect - Piping
|
Sump Sensor with positive shutdown |
7/17/2024 |
7/17/2027 |
|
Spill Contain Device
|
Single Wall Spill Bucket |
7/17/2024 |
7/17/2027 |
|
Tank
|
Fiberglass Double Wall XERXES |
Not applicable |
Not applicable |
|
Vent, Riser, Fill Piping
|
Steel risers |
Not applicable |
Not applicable |
Additional Tests
No Tests Listed
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
MFD
Motorfuel Dispensing Forms
| Facility Number |
Name |
City |
Received Date |
Letter |
|
6046596
|
Casey's #3554
|
Mulberry Grove
|
08/15/2018
|
Letter
Form
|