Notice of Violatlions (Current)
NOV Number:
E0020251613
(Pending)
Issue Date:
6/26/2025
Expiration Date:
8/25/2025
View NOV Form
Tanks |
Violations |
4, 5, 6 |
Drop tube valve or overfill alarm failed inspection. Repair or replace equipment. - Dropped tubes failed. |
4, 5, 6, 7 |
Line interstitial sensors have been raised and rendered inoperational. - Dispensers 18,20,21. Sensors must be on the bottom of the sump. |
1, 2, 3, 4, 5, 6, 7 |
Piping interstitial must be open in all sumps - Remove all jumpers. Jumpers can not be tied up. (Diesel Islands) |
NOV Number:
E0020251614
(Pending)
Issue Date:
6/26/2025
Expiration Date:
8/25/2025
View NOV Form
Tanks |
Violations |
Facility |
Miscellaneous - Each emergency stop shall be identified by a sign on all-weather materials stating "EMERGENCY STOP" in 2 inch red capital letters. |