Notice of Violations (Current)
NOV Number:
E0020251346
(Referred to Legal)
Issue Date:
5/23/2025
Expiration Date:
7/22/2025
View NOV Form
| Tanks |
Violations |
| 2 |
Annual electronic line leak detector test not completed. |
| Facility |
Annual Emergency Stop Inspection not completed or inspection report not available. |
| 1, 2 |
Annual leak detection certification not completed (Required annually). |
| 1, 2 |
Line interstitial sensor functional test not accomplished (Required annually). |
| 1 |
Mechanical line leak detector requires annual functional test. |
| Facility |
Missing copies of Annual Walkthrough Inspection Report. |
| 1, 2 |
Tank interstitial sensor functional test not accomplished (Required annually). |
NOV Number:
E0020262043
(Pending)
Issue Date:
8/11/2026
Expiration Date:
10/10/2026
View NOV Form
| Tanks |
Violations |
| Facility |
Annual Emergency Stop Inspection not completed or inspection report not available. |
| 1, 2 |
Annual leak detection certification not completed (Required annually). |
| 1, 2 |
Line interstitial sensor functional test not accomplished (Required annually). |
| Facility |
Missing copies of Annual Walkthrough Inspection Report. |
| 1, 2 |
Tank interstitial sensor functional test not accomplished (Required annually). |
IEMA Numbers Associated with the Facility
No IEMA Numbers Found
LUST
Fund Eligibility and Deductibility Determinations
No Applications Found
Tank Number 1
| Capacity: |
2500 |
|
Petroleum Use: |
Consumptive Use on Premises for Heating |
| Product: |
Diesel Fuel |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
State |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
6/26/2013 |
|
Abandoned Material: |
|
| Current Age: |
13 |
|
Abandoned Date: |
|
| Install Date: |
10/10/2012 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
10/10/2012 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Composite Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Mechanical Pressurized Line Leak Detection |
6/5/2026 |
6/5/2027 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 350 Plus |
8/1/2025 |
8/1/2026 |
|
Leak Detect - Tank
|
Non-Discriminating Interstitial Monitoring Sensors |
8/1/2025 |
8/1/2026 |
|
Overfill Prev Device
|
Overfill Alarm |
8/1/2025 |
8/1/2028 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
6/5/2026 |
6/5/2029 |
|
Piping
|
Flexible Double Wall OPW Flexworks |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
7/11/2025 |
7/11/2028 |
Leak Detect - Piping
|
Sump Sensor |
7/11/2025 |
7/11/2028 |
|
Spill Contain Device
|
Single Wall Spill Bucket |
8/1/2025 |
8/1/2028 |
|
Tank
|
Composite Double Wall Modern Welding Glasteel II |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Flexible Double Wall OPW Flexworks
|
Precision Test (Piping)
|
Pass
|
8/1/2025
|
Tank Number 2
| Capacity: |
6000 |
|
Petroleum Use: |
Back-up Generator |
| Product: |
Diesel Fuel |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
6/26/2013 |
|
Abandoned Material: |
|
| Current Age: |
13 |
|
Abandoned Date: |
|
| Install Date: |
10/10/2012 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
10/10/2012 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Composite Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Electronic Pressurized Line Leak Detection |
6/5/2026 |
6/5/2027 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 350 Plus |
8/1/2025 |
8/1/2026 |
|
Leak Detect - Tank
|
Non-Discriminating Interstitial Monitoring Sensors |
8/1/2025 |
8/1/2026 |
|
Overfill Prev Device
|
Overfill Alarm |
8/1/2025 |
8/1/2028 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
6/5/2026 |
6/5/2029 |
|
Piping
|
Flexible Double Wall OPW Flexworks |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
7/11/2025 |
7/11/2028 |
Leak Detect - Piping
|
Sump Sensor |
7/11/2025 |
7/11/2028 |
|
Piping
|
Single Wall Transition Sump |
7/11/2025 |
7/11/2028 |
Leak Detect - Piping
|
Sump Sensor |
7/11/2025 |
7/11/2028 |
|
Spill Contain Device
|
Single Wall Spill Bucket |
8/1/2025 |
8/1/2028 |
|
Tank
|
Composite Double Wall Modern Welding Glasteel II |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Flexible Double Wall OPW Flexworks
|
Precision Test (Piping)
|
Pass
|
8/1/2025
|
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
Dispenser Information
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
MFD
Motorfuel Dispensing Forms
No Forms Found