Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 6038176
Status: Active
Facility Name: St. Clair County Hwy Dept
Address: 40 N. Water Works Rd. Belleville, IL 62223
County: St. Clair
Property Parcel:
Facility Type: County
Owner Type: County
Green Tag Decal: Z003881
Green Tag Issue Date: 6/12/2024
Green Tag Expiration Date: 12/31/2026

Owner Details

Owner Name: St. Clair County Highway Dept.
Owner Address: 1415 N. Belt West Belleville, IL 62223
Owner Status: Current Owner
Purchase Date: 12/2/1998
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 3/5/2025

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Fleet 6/12/2024 12/31/2026

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0014340 St. Clair County Highway Dept. Current Owner 12/2/1998

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020253019 (Pending)    Issue Date: 11/13/2025    Expiration Date: 1/12/2026    View NOV Form

Tanks Violations
Facility Annual Emergency Stop Inspection not completed or inspection report not available.
1, 2 Annual leak detection certification not completed (Required annually).
1, 2 Document that emergency shut-off (shear valves) are in proper working order
Facility Financial responsibility must be reported yearly - Financial Responsibility must be declared annually. The form can be found at https://webapps.sfm.illinois.gov/USTPortal/Forms/FinancialResponsibility.
1, 2 Line interstitial sensor functional test not accomplished (Required annually).
1, 2 Mechanical line leak detector requires annual functional test.
Facility Missing copies of Annual Walkthrough Inspection Report.
1, 2 Overfill prevention equipment inspection(s) not completed (Required every 3 years). - Overfill drop tube is past due inspection.
1, 2 Tank interstitial sensor functional test not accomplished (Required annually).

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 10000 Diesel Fuel Currently in use Federal $0.00
2 5000 Gasoline - Regular Currently in use Federal $0.00

Dispenser Information

Name\ID Status
1/2 Active
3/4 Active

MFD Motorfuel Dispensing Forms