Notice of Violations (Current)
NOV Number:
E0020261683
(Pending)
Issue Date:
7/2/2026
Expiration Date:
8/31/2026
View NOV Form
| Tanks |
Violations |
| 1, 2 |
Miscellaneous - Fuel in dispenser containment without interstitial sensors - Remove fuel and maintain clean and dry. |
| 2 |
Water in containment without required sensors – install cathodic protection on all exposed steel piping or make containment watertight. By 10/13/28, all containments must be watertight and any CP installed in containments must be removed. - Water in the diesel STP containment sump. |
IEMA Numbers Associated with the Facility
No IEMA Numbers Found
LUST
Fund Eligibility and Deductibility Determinations
No Applications Found
Tank Number 1
| Capacity: |
10000 |
|
Petroleum Use: |
|
| Product: |
Gasoline - Regular |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
8/20/1998 |
|
Abandoned Material: |
|
| Current Age: |
28 |
|
Abandoned Date: |
|
| Install Date: |
5/12/1998 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
5/13/1998 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Electronic Pressurized Line Leak Detection |
12/18/2025 |
12/18/2026 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 350 |
12/18/2025 |
12/18/2026 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
12/18/2025 |
12/18/2028 |
|
Piping
|
Flex Connector Steel |
Not applicable |
Not applicable |
|
Piping
|
Fiberglass Single Wall Piping |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
Not applicable |
Not applicable |
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated Not Required |
Not applicable |
Not applicable |
|
Spill Contain Device
|
Single Wall Spill Bucket |
12/18/2025 |
12/18/2028 |
|
Tank
|
Fiberglass Single Wall Containment Solutions |
Not applicable |
Not applicable |
|
Vent, Riser, Fill Piping
|
Steel risers |
Not applicable |
Not applicable |
Additional Tests
No Tests Listed
Tank Number 2
| Capacity: |
10000 |
|
Petroleum Use: |
|
| Product: |
B-11 |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
8/20/1998 |
|
Abandoned Material: |
|
| Current Age: |
28 |
|
Abandoned Date: |
|
| Install Date: |
5/12/1998 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
5/13/1998 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Electronic Pressurized Line Leak Detection |
12/18/2025 |
12/18/2026 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 350 |
12/18/2025 |
12/18/2026 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
12/18/2025 |
12/18/2028 |
|
Piping
|
Flex Connector Steel |
Not applicable |
Not applicable |
|
Piping
|
Fiberglass Single Wall Piping |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
Not applicable |
Not applicable |
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated Not Required |
Not applicable |
Not applicable |
|
Spill Contain Device
|
Double Wall Spill Bucket |
12/18/2025 |
12/18/2028 |
|
Tank
|
Fiberglass Single Wall Containment Solutions |
Not applicable |
Not applicable |
|
Vent, Riser, Fill Piping
|
Steel risers |
Not applicable |
Not applicable |
Additional Tests
No Tests Listed
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
Dispenser Information
Name\ID 1/2
| Status: |
Active |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Single Wall UDC Sump |
Not applicable
|
Not applicable
|
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated Not Required |
Not applicable
|
Not applicable
|
Name\ID 3/4
| Status: |
Active |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Single Wall UDC Sump |
Not applicable
|
Not applicable
|
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated Not Required |
Not applicable
|
Not applicable
|
Name\ID 5/6
| Status: |
Active |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Single Wall UDC Sump |
Not applicable
|
Not applicable
|
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated Not Required |
Not applicable
|
Not applicable
|
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
MFD
Motorfuel Dispensing Forms
No Forms Found