Notice of Violatlions (Current)
NOV Number:
E0020260004
(Pending)
Issue Date:
1/5/2026
Expiration Date:
3/6/2026
View NOV Form
| Tanks |
Violations |
| Facility |
Missing copies of current testing certificates for operator training - No valid "C" Operator certificates. |
| 1, 2 |
Spill prevention equipment device is in disrepair and requires replacement. - Cracks in spill buckets for tanks 1 & 2. |
| 1, 2 |
Tank monitor does not appear to function properly and requires maintenance. - Power light is out on the ATG. Must repair. |
| 2 |
Water in containment without required sensors – install cathodic protection on all exposed steel piping or make containment watertight. By 10/13/28, all containments must be watertight and any CP installed in containments must be removed. |