Notice of Violatlions (Current)
NOV Number:
E0020251934
(Pending)
Issue Date:
8/1/2025
Expiration Date:
9/30/2025
View NOV Form
Tanks |
Violations |
Facility |
Financial responsibility must be reported yearly - Financial Responsibility must be declared annually. The form can be found at https://webapps.sfm.illinois.gov/USTPortal/Forms/FinancialResponsibility. |
3, 4, 5 |
Line interstitial sensors have been raised and rendered inoperational. - Dispenser 7/8 and 9/10 have raised sensors. The sensors must be at the lowest part of the sump. |
3, 4, 5 |
Tank monitor does not appear to function properly and requires maintenance. - Printer is not working. |
3, 4, 5 |
Water in dispenser containment with interstitial sensors - Remove water and repair containments to prevent water ingress - Dispensers 7/8 and 9/10 contain water. |