11, 12, 13 |
Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - Lock rings for all containment sump lids are deterioriated and must be replaced. |
13 |
Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - STP sump lid has caved in and will not seal properly. Must replace. |
14 |
Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - Lock rings for all containment sump lids are deterioriated and must be replaced. |
11 |
Install or replace lockable fill pipe caps. - ATG probe riser cap for tank 11 RUL is corroded andwill not lock back into place. Must replace. |
12, 13 |
Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. |