Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 5044830
Status: Active
Facility Name: Road Ranger #181
Address: 500 Toronto Road
Springfield, IL 62703
County: Sangamon
Property Parcel: 22-33.0-200-040
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y000744
Green Tag Issue Date: 5/4/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: Road Ranger, LLC
Owner Address: 1501 Woodfield Rd., Suite 300 S
Schaumburg, IL 60173
Owner Status: Current Owner
Purchase Date:
Type of Financial Responsibility: Self-Insurance
Financial Responsibility Reporting Due Date: 6/28/2025

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 5/4/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0033990 Road Ranger, LLC Current Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violations (Current)

NOV Number: E0020250819 (Pending)    Issue Date: 3/27/2025    Expiration Date: 5/26/2025    View NOV Form

Tanks Violation
Facility Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable

NOV Number: E0020250820 (Pending)    Issue Date: 3/27/2025    Expiration Date: 5/26/2025    View NOV Form

Tanks Violation
1, 2, 3, 4, 5, 6, 7 Line interstitial sensors have been raised and rendered inoperational. - Dispenser 5/6 and 29/28S.
Facility Miscellaneous - Shear valve leaking on dispenser 5/6 and 29/28S. Fluids in the containment. Repair or replace to prevent further release. Section 175.720 Defective or Non-Compliant Equipment and Emergency Action by OSFM a)Pursuant to Section 6 of the Gasoline Storage Act [430 ILCS 15/6], whenever necessary or appropriate to assure that the public health or safety is not threatened, OSFM shall have the authority to undertake emergency action whenever there is a release or substantial threat of a release of petroleum or regulated substances from a UST.
1, 2, 3, 4, 5, 6, 7 Overfill prevention equipment inspection(s) not completed (Required every 3 years). - Overfill alarm testing on all tanks and Ball Float testing on Tanks 1-6 expired 1/24/2025.
4, 6 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.
1, 2, 3, 4, 5, 6, 7 Triennial spill prevention equipment testing not completed. - Expired 9/17/2024.
1, 2, 3, 4, 5, 6, 7 Triennial testing for qualifying piping containment sump not completed (Required every 3 years). - Expired 9/17/2024.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 20000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 12/29/2011 Abandoned Material:
Current Age: 13 Abandoned Date:
Install Date: 8/31/2011 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 9/6/2011

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 3/20/2025 3/20/2026
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 3/20/2025 3/20/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 3/20/2025 3/20/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 3/19/2025 3/19/2026
Leak Detect - Tank SIR and Prec Tightness Testing Warren Rogers Assoc. Petro Network S3 Version D 4/30/2024 4/30/2025
Overfill Prev Device Ball Float Vent Valve OPW 53VML 1/24/2022 1/24/2025
Overfill Prev Device Overfill Alarm 1/24/2022 1/24/2025
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 9/17/2021 9/17/2024
Leak Detect - Piping Sump Sensor with positive shutdown 3/19/2025 3/19/2026
Piping Single Wall STP/Tanktop Sump 9/17/2021 9/17/2024
Leak Detect - Piping Sump Sensor with positive shutdown 3/19/2025 3/19/2026
Spill Contain Device Double Wall Spill Bucket 9/17/2021 9/17/2024
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 3/20/2025
Tank Fiberglass Double Wall XERXES Precision Test (Tank) Pass 3/20/2025



Tank Number 2

Capacity: 20000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 12/29/2011 Abandoned Material:
Current Age: 13 Abandoned Date:
Install Date: 8/31/2011 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 9/6/2011

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 3/20/2025 3/20/2026
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 3/20/2025 3/20/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 3/20/2025 3/20/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 3/20/2025 3/20/2026
Leak Detect - Tank SIR and Prec Tightness Testing Warren Rogers Assoc. Petro Network S3 Version D 4/30/2024 4/30/2025
Overfill Prev Device Ball Float Vent Valve OPW 53VML 1/24/2022 1/24/2025
Overfill Prev Device Overfill Alarm 1/24/2022 1/24/2025
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 9/17/2021 9/17/2024
Leak Detect - Piping Sump Sensor with positive shutdown 3/19/2025 3/19/2026
Piping Single Wall STP/Tanktop Sump 9/17/2021 9/17/2024
Leak Detect - Piping Sump Sensor with positive shutdown 3/19/2025 3/19/2026
Spill Contain Device Double Wall Spill Bucket 9/17/2021 9/17/2024
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 3/20/2025
Tank Fiberglass Double Wall XERXES Precision Test (Tank) Pass 3/20/2025



Tank Number 3

Capacity: 12000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 12/29/2011 Abandoned Material:
Current Age: 13 Abandoned Date:
Install Date: 8/31/2011 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 9/6/2011

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 3/20/2025 3/20/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 3/20/2025 3/20/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 3/19/2025 3/19/2026
Overfill Prev Device Ball Float Vent Valve OPW 53VML 1/24/2022 1/24/2025
Overfill Prev Device Overfill Alarm 1/24/2022 1/24/2025
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 9/17/2021 9/17/2024
Leak Detect - Piping Sump Sensor with positive shutdown 3/19/2025 3/19/2026
Spill Contain Device Double Wall Spill Bucket 9/17/2021 9/17/2024
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 3/20/2025
Tank Fiberglass Double Wall XERXES Precision Test (Tank) Pass 3/20/2025



Tank Number 4

Capacity: 8000 Petroleum Use:
Product: E85 CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 12/29/2011 Abandoned Material:
Current Age: 13 Abandoned Date:
Install Date: 8/31/2011 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 9/6/2011

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 3/20/2025 3/20/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 3/20/2025 3/20/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 3/19/2025 3/19/2026
Overfill Prev Device Ball Float Vent Valve OPW 53VML 1/24/2022 1/24/2025
Overfill Prev Device Overfill Alarm 1/24/2022 1/24/2025
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 9/17/2021 9/17/2024
Leak Detect - Piping Sump Sensor with positive shutdown 3/19/2025 3/19/2026
Spill Contain Device Double Wall Spill Bucket 9/17/2021 9/17/2024
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 3/20/2025
Tank Fiberglass Double Wall XERXES Precision Test (Tank) Pass 4/30/2024



Tank Number 5

Capacity: 15000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 12/29/2011 Abandoned Material:
Current Age: 13 Abandoned Date:
Install Date: 8/31/2011 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 9/6/2011

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 3/20/2025 3/20/2026
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 3/20/2025 3/20/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 3/20/2025 3/20/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 3/19/2025 3/19/2026
Overfill Prev Device Ball Float Vent Valve OPW 53VML 1/24/2022 1/24/2025
Overfill Prev Device Overfill Alarm 1/24/2022 1/24/2025
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 9/17/2021 9/17/2024
Leak Detect - Piping Sump Sensor with positive shutdown 3/19/2025 3/19/2026
Piping Single Wall STP/Tanktop Sump 9/17/2021 9/17/2024
Leak Detect - Piping Sump Sensor with positive shutdown 3/19/2025 3/19/2026
Spill Contain Device Double Wall Spill Bucket 9/17/2021 9/17/2024
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 3/20/2025
Tank Fiberglass Double Wall XERXES Precision Test (Tank) Pass 4/30/2024



Tank Number 6

Capacity: 10000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 12/29/2011 Abandoned Material:
Current Age: 13 Abandoned Date:
Install Date: 8/31/2011 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 9/6/2011

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 3/20/2025 3/20/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 3/20/2025 3/20/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 3/19/2025 3/19/2026
Overfill Prev Device Ball Float Vent Valve OPW 53VML 1/24/2022 1/24/2025
Overfill Prev Device Overfill Alarm 1/24/2022 1/24/2025
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 9/17/2021 9/17/2024
Leak Detect - Piping Sump Sensor with positive shutdown 3/19/2025 3/19/2026
Spill Contain Device Double Wall Spill Bucket 9/17/2021 9/17/2024
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 3/20/2025
Tank Fiberglass Double Wall XERXES Precision Test (Tank) Pass 4/30/2024



Tank Number 7

Capacity: 20000 Petroleum Use:
Product: B-99 CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 12/29/2011 Abandoned Material:
Current Age: 13 Abandoned Date:
Install Date: 8/31/2011 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 9/6/2011

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping European with No Test Req Suction N/A N/A
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 3/20/2025 3/20/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 3/19/2025 3/19/2026
Leak Detect - Tank SIR and Prec Tightness Testing Warren Rogers Assoc. Petro Network S3 Version D 4/30/2024 4/30/2025
Overfill Prev Device Overfill Alarm 1/24/2022 1/24/2025
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 9/17/2021 9/17/2024
Leak Detect - Piping Sump Sensor with positive shutdown 3/19/2025 3/19/2026
Spill Contain Device Double Wall Spill Bucket 9/17/2021 9/17/2024
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 4/30/2024
Tank Fiberglass Double Wall XERXES Precision Test (Tank) Pass 3/20/2025

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/17/2021 9/17/2024
Leak Detect - Piping Sump Sensor with positive shutdown 3/19/2025 3/19/2026



Name\ID 11/12

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/17/2021 9/17/2024
Leak Detect - Piping Sump Sensor with positive shutdown 3/19/2025 3/19/2026



Name\ID 13/14

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/17/2021 9/17/2024
Leak Detect - Piping Sump Sensor with positive shutdown 3/19/2025 3/19/2026



Name\ID 15/16

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/17/2021 9/17/2024
Leak Detect - Piping Sump Sensor with positive shutdown 3/19/2025 3/19/2026



Name\ID 17/18

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/17/2021 9/17/2024
Leak Detect - Piping Sump Sensor with positive shutdown 3/19/2025 3/19/2026



Name\ID 18 Diesel

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/17/2021 9/17/2024
Leak Detect - Piping Sump Sensor with positive shutdown 3/19/2025 3/19/2026



Name\ID 19

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/17/2021 9/17/2024
Leak Detect - Piping Sump Sensor with positive shutdown 3/19/2025 3/19/2026



Name\ID 20

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/17/2021 9/17/2024
Leak Detect - Piping Sump Sensor with positive shutdown 3/19/2025 3/19/2026



Name\ID 21

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/17/2021 9/17/2024
Leak Detect - Piping Sump Sensor with positive shutdown 3/19/2025 3/19/2026



Name\ID 22

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/17/2021 9/17/2024
Leak Detect - Piping Sump Sensor with positive shutdown 3/19/2025 3/19/2026



Name\ID 23

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/17/2021 9/17/2024
Leak Detect - Piping Sump Sensor with positive shutdown 3/19/2025 3/19/2026



Name\ID 23 Slave

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/17/2021 9/17/2024
Leak Detect - Piping Sump Sensor with positive shutdown 3/19/2025 3/19/2026



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/17/2021 9/17/2024
Leak Detect - Piping Sump Sensor with positive shutdown 3/19/2025 3/19/2026



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/17/2021 9/17/2024
Leak Detect - Piping Sump Sensor with positive shutdown 3/19/2025 3/19/2026



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/17/2021 9/17/2024
Leak Detect - Piping Sump Sensor with positive shutdown 3/19/2025 3/19/2026



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/17/2021 9/17/2024
Leak Detect - Piping Sump Sensor with positive shutdown 3/19/2025 3/19/2026